5.9 Initialization
When you’d like to return the inner memory to default setting at factory shipment, initialize it.
After initialization, in master, slave registration and routing setting information data will be deleted.
And in slave, its Unit No. setting, registered, is deleted.
Setting of wireless unit
Operating mode switch
Be sure to set to “SET”.
Select from “00
~
F5”.
※
1
Communication channel
Unit No. switch
Any settings are OK.
Be sure to set No.9 ON. Except it, any settings are
OK. Refer to <3.2.4 Setting of MODE switch>
MODE switch
※
1: At initialization, it doesn’t communicate by wireless. Therefore any communication channel
setting is OK.
Procedures for initialization
(1) Set all switches as above.
(2) Turn power supply of wireless unit to initialize on.
(Blinking “ALARM” means it is the state to prepare for initialization.)
Master
Slave
(3) Press <ENTER> switch continuously (approx. 3 sec).
(
4) LED is blinking as below.
Master
Slave
(5) Initialization is completed when LED lights as below.
(
Blinking “ALARM” means that MODE switch No.9 is kept to ON.)
Master
Slave
(6) After completing the initialization, be sure to set MODE switch No.9 to OFF. After that, turn
power supply on again or change operating mode switch.
Lighting Blinking Blinking
Lighting Lighting Blinking Blinking
Lighting Blinking
Lighting Lighting Blinking
Lighting Lighting Lighting Blinking
Lighting Lighting Blinking
5-39
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: [email protected]
Содержание KR20
Страница 1: ...Phone 800 894 0412 Fax 888 723 4773 Web www ctiautomation net Email info ctiautomation net ...
Страница 4: ...Phone 800 894 0412 Fax 888 723 4773 Web www ctiautomation net Email info ctiautomation net ...
Страница 10: ...1 6 Phone 800 894 0412 Fax 888 723 4773 Web www ctiautomation net Email info ctiautomation net ...
Страница 117: ...9 1 Chapter 9 Specifications Phone 800 894 0412 Fax 888 723 4773 Web www ctiautomation net Email info ctiautomation net ...