3.2.2 Setting of communication channel
※
At factory setting, it’s set to “00”.
Select the communication channel from ”00
~
F5”.
Adding to the fixed channel, 76ch(00
~4
B), 89 group channel can be selected.
Group channel is the function that it selects connectable channel from several fixed channels
automatically. When using repeater function, use with the fixed channels.
When using group channel, settable channel numbers are decreased in the same communication
area and the communication time is longer.
Master, slaves, repeaters in the same wireless system should be set to the same channel.
Setting of communication channel will be available when turning power on again or changing
operating mode switch.
Note
:
When using several channels in the same communication area, check there are no
influences each other. It differs from the mounting conditions; max 15 channels are
used as a standard. Do not use adjoining channels and use channel that separates
5 or more (recommended).
3.2.3 Setting of Unit No. (Master, Slave)
※
At factory setting, it’s set to “00”.
Set Unit No. for master to “00”, for slaves and repeaters to “01
~
99”.
With 1:1 topology, be sure to set it for slave to “01”. If not, it cannot communicate.
Note: Within the same wireless system (same master), do not set the same Unit No. for
several slaves. In addition, there is the function to prevent double registration for
slave. (Slave double registration) Refer to <4. Register slave> in detail.
3.2.4 Setting of MODE switches
※
At factory setting, it’s set as left figures.
Set the setting of available/not available by 1:N topology setup, switch
RS232C/RS485, Available/Not available of data holding, communication
conditions.
・
When setting of 1:1 topology, you can use as same as the setting during operation.
・
When setting of 1:1 topology with repeaters or 1:N topology, select RS232C for serial
communication selection. It is required to use setting tool.
3-5
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: [email protected]
Содержание KR20
Страница 1: ...Phone 800 894 0412 Fax 888 723 4773 Web www ctiautomation net Email info ctiautomation net ...
Страница 4: ...Phone 800 894 0412 Fax 888 723 4773 Web www ctiautomation net Email info ctiautomation net ...
Страница 10: ...1 6 Phone 800 894 0412 Fax 888 723 4773 Web www ctiautomation net Email info ctiautomation net ...
Страница 117: ...9 1 Chapter 9 Specifications Phone 800 894 0412 Fax 888 723 4773 Web www ctiautomation net Email info ctiautomation net ...