8-2
8.1 ALARM indication
This is the explanation about wireless unit ALARM indication.
ALARM indication means the below cautions and error according to the operating mode.
In case of operating mode is “TEST”, it has another meanings not cautions or error. Please refer to
<
6.2 Test functions of main unit
>
.
Reference
:
<6.2 Test functions of main unit>
When operating mode is “SET”
ALARM indication
Meaning
Troubleshooting
Command error when
command not for wireless
unit is input
Delete this data by wireless unit.
In case of operating mode is “SET”, wire
communication can be used with only
setting tool. In order to do normal
communication, set to “RUN”.
Light for a moment
Communication error with
setting tool
Refer to dialog by setting tool.
Blinking
Cautions to show during
initializing mode (MODE
switch No.9 is ON.)
Set MODE switch No.9 OFF and turn
power on again.
When slave
registration
Blinking
Error to indicate failure of
slave registration
Refer to
<
Chapter 4 Resister slave
>
about how to register slave
When initializing
Cautions to show during
initializing mode
Check with
<
5.9 Initialization
>
Blinking
When operating mode is “RUN”
ALARM indication
Meaning
Troubleshooting
Light for a moment
Communication error and
data are deleted
Refer to <8.2 Troubleshooting>
Error to show that slave
isn’t registered.
Register slave
Error to show that routing
setting is not set.
Set routing setting
Lighting
continuously
With 1:1 topology, MODE
switch No.1 is ON.
When 1:1 topology, set MODE switch
No.1 to OFF.
With I/O type,
When outputing
communication error
(Lighting communication
error LED)
It can’t communicate by wireless
communication. Check power supply,
communication setting, mounting place,
radio wave conditions and so on of both
sides.
※
When operating mode is “RUN”, error contents can be read out by using setting tool.
Note: When it lights for a moment, it keeps communication, however, when it lights
continuously, it can’t communicate.
Reference
:
<6.3.6 Read log> <Help in setting tool (Configurator KR)>
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: [email protected]
Содержание KR20
Страница 1: ...Phone 800 894 0412 Fax 888 723 4773 Web www ctiautomation net Email info ctiautomation net ...
Страница 4: ...Phone 800 894 0412 Fax 888 723 4773 Web www ctiautomation net Email info ctiautomation net ...
Страница 10: ...1 6 Phone 800 894 0412 Fax 888 723 4773 Web www ctiautomation net Email info ctiautomation net ...
Страница 117: ...9 1 Chapter 9 Specifications Phone 800 894 0412 Fax 888 723 4773 Web www ctiautomation net Email info ctiautomation net ...