12-2
12.1
61B
Settings and Operations of Stop Functions
Following stop functions are available during operations. Each deceleration time can be set individually.
Set the deceleration time according to each occurrence condition of the stop operation.
Name
Occurrence condition
Axis stopped
Operation
Deceleration
stop
when the deceleration
stop contact turns on
Each axis
Stops in deceleration time of the control
being operated.
Pause
when the deceleration
stop contact turns on
Each axis
Stops in deceleration time of the control
being operated, and restarts the stopped
control once the deceleration stop is
reset.
Emergency
stop
when the emergency stop
contact turns on
Each axis
Stops in the emergency stop
deceleration time.
Limit stop
when the input of limit
switch turns on
Each axis
Stops in the limit stop deceleration time.
Software limit
stop
when exceeding the range
of the software limit
Each axis
Error stop
when an error occurred
Each axis
Stops in the error stop deceleration time.
System stop
when the system stop
contact turns on
All axes
Stops without deceleration time
The deceleration stop (pause), emergency stop and system stop is performed by turning on each
request contact in the I/O area. The stopped state is held while each contact is on until each request
signal turns off. Any operation cannot be performed in the stopped state.
Refer to the following table for the stop by turning contacts on. It indicates the allocated I/O when the
FP
Σ
/FP2 positioning unit RTEX is installed in the slot 0.
Contact allocation Target
axis
Name
Descriptions
FP
Σ
FP2
Y100 Y80 All axes System stop
Contact for requesting the system stop. When it turns on, all
axes will stop with 0-deceleration time.
WY
13
Y130
WY
11
Y110 1 axis
Emergency stop
Requests the emergency stop for the corresponding AMP.
The deceleration time for the emergency stop is specified by
Configurator PM or the emergency stop setting in the shared
memory.
(The operation is the level type.)
Note) The deviation counter cannot be cleared.
Y131
Y111 2 axis
Y132
Y112 3 axis
Y133
Y113 4 axis
Y134
Y114 5 axis
Y135
Y115 6 axis
Y136
Y116 7 axis
Y137
Y117 8 axis
Y138
Y118 1 axis
Deceleration stop
Requests the deceleration stop for the corresponding AMP.
The deceleration time for the deceleration stop is specified by
Configurator PM or the deceleration stop setting in the shared
memory.
(The operation is the level type.)
Note) The deviation counter cannot be cleared.
Y139
Y119 2 axis
Y13A
Y11A 3 axis
Y13B
Y11B 4 axis
Y13C
Y11C 5 axis
Y13D
Y11D 6 axis
Y13E
Y11E 7 axis
Y13F
Y11F 8 axis
Содержание FP2 Positioning Unit RTEX
Страница 1: ......
Страница 6: ...iv ...
Страница 14: ...xii ...
Страница 15: ...Chapter 1 Functions of Unit and Restrictions on Combination ...
Страница 21: ...Chapter 2 Parts and Functions ...
Страница 22: ...2 2 2 1 Parts and Functions FPΣ Positioning Unit RTEX FP2 Positioning Unit RTEX ...
Страница 24: ...2 4 ...
Страница 25: ...Chapter 3 Wiring ...
Страница 27: ...3 3 3 2 Network Connector RJ45 plug is connected to the network connector Pins of RJ45 plug Connecting diagram ...
Страница 31: ...Chapter 4 Power On Off and Items to Check ...
Страница 36: ...4 6 ...
Страница 37: ...Chapter 5 4BPreparation For Operation ...
Страница 45: ...Chapter 6 5BI O Allocation ...
Страница 53: ...Chapter 7 6BSetting Tool Configurator PM ...
Страница 83: ...7 31 Setting Font Select Option Font in the menu bar The following dialog is shown ...
Страница 102: ...7 50 ...
Страница 103: ...Chapter 8 7BAutomatic Operation Position Control ...
Страница 118: ...8 16 ...
Страница 119: ...8 17 When the X axis and Y axis is the moving axes each axis in the above diagram is replaced ...
Страница 141: ...Chapter 9 8BManual Operation JOG Operation ...
Страница 146: ...9 6 ...
Страница 147: ...Chapter 10 9BManual Operation Home Return ...
Страница 155: ...Chapter 11 10BManual Operation Pulser Operation ...
Страница 159: ...Chapter 12 11BStop Functions ...
Страница 162: ...12 4 ...
Страница 163: ...Chapter 13 12BSupplementary Functions ...
Страница 177: ...13 15 Sample program When reading AMP parameter No 1 1 of axis 1 with A6N or A5N ...
Страница 179: ...13 17 Sample program When writing AMP parameter No 1 1 of axis 1 with A6N or A5N ...
Страница 183: ...Chapter 14 Precautions During Programming ...
Страница 187: ...Chapter 15 Errors and Warnings ...
Страница 212: ...15 26 ...
Страница 213: ...Chapter 16 Troubleshooting ...
Страница 214: ...16 2 16 1 Cannot Communication With AMP ...
Страница 215: ...Chapter 17 Specifications ...
Страница 275: ...Chapter 18 Dimensions ...
Страница 276: ...18 2 18 1 FPSigma Positioning Unit RTEX ...
Страница 277: ...18 3 18 2 FP2 Positioning Unit RTEX ...
Страница 278: ...18 4 ...
Страница 279: ...Chapter 19 Sample Programs ...
Страница 283: ...19 5 ...
Страница 286: ...19 8 ...
Страница 288: ......