8-31
8.3.5
132B
Operation of Master and Slave Axes
Operation of master and slave axes
Various positioning parameters should be set to perform operations on the positioning unit. The
parameters to be applied vary in the synchronous operation as follows.
Parameter name
Operation during synchronous operation
Unit setting
Operates by the setting of each axis.
Specify the same settings for the axes to be
synchronized when performing the synchronous
operation.
Pulse number per rotation
Moving amount per rotation
Pulse I/O setting
Limit switch
Follows the operation of the master axis during the
synchronous operation.
Limit switch connection
Software limit (Positioning control)
Software limit (Home return)
Software limit (JOG operation)
Upper limit of software limit
Lower limit of software limit
Auxiliary output mode
Auxiliary output ON time (ms)
Auxiliary output Delay rate
Home return – Setting code
Varies depending on the operation mode of the
synchronous operation.
Synchronous mode A: Operates by the setting of
each axis.
Synchronous mode B: Follows the operation of a
master axis.
Home return – Direction
Home return – Acceleration time
Home return – Deceleration time
Home return – Target speed
Home return – Creep speed
JOG operation – Acceleration/Deceleration type
Follows the operation of the master axis during the
synchronous operation.
JOG operation – Acceleration time
JOG operation – Deceleration time
JOG operation – Target speed
JOG positioning operation setting code
JOG positioning operation acceleration time
JOG positioning operation deceleration time
JOG positioning operation target speed
Emergency stop deceleration time (ms)
The operation varies according to the type of stop
operations.
For the details, see the following “Stop function in
synchronous operation”.
Limit stop deceleration time (ms)
Error stop deceleration time (ms)
Pulser operation setting code
Operates by the setting of each axis.
Specify the same settings for the axes to be
synchronized when performing the synchronous
operation.
Pulser operation ratio numerator
Pulser operation ratio denominator
Stop function in synchronous operation
If the stop operation is executed for the master and slave axes during the synchronous operation, the
operation is as follows.
Axis requested to stop
Stop operation
Operational overview
Master axis
Slave axis
System stop
All axes stop without
deceleration time.
All axes stop.
Emergency stop
Deceleration stop
A specified axis stops with
a deceleration time.
Stops with the deceleration time for the master axis.
Limit stop
Stops with a deceleration
time when a limit occurred. Stops with the deceleration time for the master axis.
After stop, the error code occurred on the master
axis is set for the master/slave axes.
Error stop
Stop the operation with a
deceleration time when an
error occurs.
Содержание FP2 Positioning Unit RTEX
Страница 1: ......
Страница 6: ...iv ...
Страница 14: ...xii ...
Страница 15: ...Chapter 1 Functions of Unit and Restrictions on Combination ...
Страница 21: ...Chapter 2 Parts and Functions ...
Страница 22: ...2 2 2 1 Parts and Functions FPΣ Positioning Unit RTEX FP2 Positioning Unit RTEX ...
Страница 24: ...2 4 ...
Страница 25: ...Chapter 3 Wiring ...
Страница 27: ...3 3 3 2 Network Connector RJ45 plug is connected to the network connector Pins of RJ45 plug Connecting diagram ...
Страница 31: ...Chapter 4 Power On Off and Items to Check ...
Страница 36: ...4 6 ...
Страница 37: ...Chapter 5 4BPreparation For Operation ...
Страница 45: ...Chapter 6 5BI O Allocation ...
Страница 53: ...Chapter 7 6BSetting Tool Configurator PM ...
Страница 83: ...7 31 Setting Font Select Option Font in the menu bar The following dialog is shown ...
Страница 102: ...7 50 ...
Страница 103: ...Chapter 8 7BAutomatic Operation Position Control ...
Страница 118: ...8 16 ...
Страница 119: ...8 17 When the X axis and Y axis is the moving axes each axis in the above diagram is replaced ...
Страница 141: ...Chapter 9 8BManual Operation JOG Operation ...
Страница 146: ...9 6 ...
Страница 147: ...Chapter 10 9BManual Operation Home Return ...
Страница 155: ...Chapter 11 10BManual Operation Pulser Operation ...
Страница 159: ...Chapter 12 11BStop Functions ...
Страница 162: ...12 4 ...
Страница 163: ...Chapter 13 12BSupplementary Functions ...
Страница 177: ...13 15 Sample program When reading AMP parameter No 1 1 of axis 1 with A6N or A5N ...
Страница 179: ...13 17 Sample program When writing AMP parameter No 1 1 of axis 1 with A6N or A5N ...
Страница 183: ...Chapter 14 Precautions During Programming ...
Страница 187: ...Chapter 15 Errors and Warnings ...
Страница 212: ...15 26 ...
Страница 213: ...Chapter 16 Troubleshooting ...
Страница 214: ...16 2 16 1 Cannot Communication With AMP ...
Страница 215: ...Chapter 17 Specifications ...
Страница 275: ...Chapter 18 Dimensions ...
Страница 276: ...18 2 18 1 FPSigma Positioning Unit RTEX ...
Страница 277: ...18 3 18 2 FP2 Positioning Unit RTEX ...
Страница 278: ...18 4 ...
Страница 279: ...Chapter 19 Sample Programs ...
Страница 283: ...19 5 ...
Страница 286: ...19 8 ...
Страница 288: ......