Electrode-specific configuration – pH
For configuration of pH electrodes.
Autodos M1-3 with acid or alkali dosing:
press the buttons
Set value
[13] +
Function
[11].
Autodos M3 with acid dosing
:
press the buttons
Set acid
[11] +
Select function
[7].
Autodos M3 with alkali dosing
:
press the buttons
Set alk/chlor
[13] +
Select function
[7].
This is indicated via the text “
SEt ACi
” or “
SEt bAS
” (depending on whether acid or alkali dosing is selected) and flashing of the
“
Off
” and “
Auto
” LEDs.
To exit configuration, press the
Cal.
button [0] or scroll past the last line.
The following can be modified in the channel-specific configuration – pH:
Line
Text
Setting
Explanation
-01
doS
Selection of dosing outlet and function.
oFF
No dosing.
ono*
On-/Off-dosing.
Pdo
Pulse width dosing.
FrE
Frequency dosing.
Cur
Dosing via current output.
-02
P
0.10–2.00 (0.20*)
pH
P-band. (Pdo, FrE, Cur)
-03
I
000–100 (000*)
minutes
I-time, 000 = no I-regutlation. (Pdo, FrE, Cur)
-04
d
000–100 (000*)
secondes
D-time, 000 = no D-regulation. (Pdo, FrE, Cur)
-05
dF
010–180 (100*)
strokes/minute
Max. frequency dosing. (FrE)
-06
Pdo
005–015 (010*)
minutes
Pulse width during pulse width dosing. (Pdo)
-07
Ldt
000–060 (000*)
minutes
Long dosing time alarm, 0 = no function.
-08
oFt
000–600 (000*)
seconds
Min. time OFF for relay, 0 = no function. (ono)
-09
ont
000–600 (000*)
seconds
Min. time ON for relay, 0 = no function. (ono)
-10
Cur
- - 0 / - - 4 (- - 4*)
Current output, selection of range 0–20 mA/4–20 mA.
-11
C-L
0.00–9.99 (6.00*) pH
Current output, value for 0/4 mA
-12
C-H
0.00–9.99 (8.50*) pH
Current output, value for 20 mA.
-13
AHd
005–600 (005*)
seconds
Delay time for high alarm.
-14
ALd
005–600 (005*)
seconds
Delay time for low alarm
* Factory default!