Configuration – Autodos M3 free chlorine, redox, pH
Line
Text
Setting
Explanation
-01
FLo
Selection of flow switch and alarm for low flow.
oFF
No flow switch. Flow alarm OFF.
Son
Flow switch that closes with flow. Flow alarm ON.
Pof
Turbine flow meter. Flow alarm OFF.
Pon*
Turbine flow meter. Flow alarm ON.
-02
FCL
Selection of electrode type for chlorine measurement.
Pb*
PB200, CLE2.2 or redox.
Cur
4–20mA sensor e.g. CLE3.
-03
FCC
Selection of compensation of free chlorine against flow and/or pH.
non
No compensation.
Flo
Compensated against flow.
PH-
Compensated against pH.
FPH*
Compensated against flow and pH.
-04
PHc
Selection of pH calibration point 2.
Calibration point 1 = pH 7.00
PH9*
Calibration point 2 = pH 9.00
PH4
Calibration point 2 = pH 4.00
-05
PC
Setting of access from PC.
No*
No access (display only).
rES
Alarm reset only.
Prg
Fully programmable.
-06
Sio
001-255 (001*)
Selection of Modbus ID number
-07
FLd
000-030 (000*) [minuter]
Flow alarm delay time.
-08
rEL
000-030 (000*) [minuter]
Alarm relay delay time.
-09
SbY
The SbY input blocks all dosing plus the alarm relay.
rEL*
Activates the alarm.
non
Does not activate the alarm.
* Factory default!