11
230 VAC N
230 VAC L
ENGLISH
Autodos M
MA60-10E
ENGLISH
Autodos M
MA60-10E
Connection example - Autodos M2
GND free chlorine
Current input free chlorine (4–20mA)
24 VDC
Flow meter (white cable)/ – GND current outputs
Current output 1 (pH) 4–20 mA (0–20 mA)
Current output 2 (redox/chlorine) 4–20mA (0–20mA)
PNP in STDBY
Flow meter (green cable)/NPN in flow switch
PNP in, level switch (alarm upon closed input)
Flow meter (brown cable)/16 VDC PNP input
–GND temperature sensor
Temperature sensor
Twin-cable communication with PC
Alarm (common)
de-energized state
230 VAC L
Chlorine dosing (free)
230 VAC L
Acid/alkali dosing
PB200 chlorine electrode
Chlorine electrodeCLE2.2
GND
V–
V+
Connection of ProMinent CLE 3-mA 10ppm
Terminal 1 (+) to terminal 26
Terminal 2 (–) to terminal 27
Accessories
Modelbus RTU
9600 band, Parity None
Example D:
Current
output
controlled
dosing pump
Example A:
On/Off
controlled
dosing pump
Example C:
Frequency
controlled
dosing pump
Connection example - Autodos M3
GND combined chlorine
Current input combined chlorine (4–20mA)
24 VDC
GND free chlorine
Current input free chlorine (4–20mA)
24 VDC
Flow meter (white cable)/ – GND current outputs
Current output 1 (pH) 4–20mA (0–20mA)
Current output 2 (combined chlorine) 4–20mA (0–20mA)
Current output 3 (free chlorine) 4–20mA (0–20mA)
PNP in STDBY
Flow meter (green cable)/NPN in flow switch
PNP in, level switch (alarm upon closed input)
Flow meter (brown cable)/16 VDC PNP input
–GND temperature sensor
Temperature sensor
Twin-cable communication with PC
Alarm (common)
de-energized state
230 VAC L
Chlorine dosing (free)
230 VAC L, Chlorine
dosing (combined)
230 VAC L
Acid/alkali dosing
PB200 chlorine
electrode
Chlorine electrode CLE2.2
GND
V–
V+
Connection of ProMinent CTE 1-mA 10ppm
Terminal 1 (+) to terminal 29
Terminal 2 (–) to terminal 30
Connection of ProMinent CLE 3-mA 10ppm
Terminal 1 (+) to terminal 26
Terminal 2 (–) to terminal 27
Accessories
Modelbus RTU
9600 band, Parity None
Example D:
Current
output
controlled
dosing pump
Example A:
On/Off
controlled
dosing pump
Example C:
Frequency
controlled
dosing pump
230 VAC L
Acid dosing
230 VAC L
Alkali dosing
230 VAC L
Chlorine dosing (free)
Alarm (common)
de-energized state
M3 - free chlorine, redox, pH
M3 - free chlorine, combined chlorine, pH