8. Startup guide
This is a short check list with the different steps needed to get started with Autodos. References are given to the sections in the
manual relevant for each step. Still, read through the whole manual to have a complete picture of how the system works and all
its setting possibilities.
1.
Install the Autodos unit,
see section 7 Installation pipes.
2.
Check
that you have the correct electrode kit for your valve, see below.
Autodos
Elektrodkit
M1
416500 - Free chlorine
416501 - PB200 Free chlorine
416500 - Free chlorine
416502 - CLE3 10ppm Free chlorine
416510 - pH
416511 - pH
416520 - Redox
416521 - Redox
416530 - Total chlorine
416531 - CTE1 Total chlorine
M2
416540 - Free chlorine , pH
416541 - PB200 Free chlorine & pH
416540 - Free chlorine , pH
416542 - CLE3 10ppm Free chlorine & pH
416540 - Free chlorine , pH
416543 - CLE3 20ppm Free chlorine & pH
416550 - Redox, pH
416551 - Redox pH
M3
416560 - Free chlorine , Redox, pH
416561 - Free chlorine PB200, Redox & pH
416560 - Free chlorine , Redox, pH
416562 - Free chlorine CLE3 10ppm, Redox & pH
416570 - Free chlorine , Combined chlorine, pH
416571 - Free chlorine , Combined chlorine, pH
3.
Install the electrodes
and the installation kit with connector details in the corresponding measuring cell in the valve, see
page 6. An instruction showing how the details of the installation kit shall be connected is included in each respective kit.
NOTE! The electrodes can not be dry or be exposed to frost or quick temperature changes. For more information about the
electrodes, please see the instruction “Handling and care of electrodes” which is enclosed with the electrode kit.
4.
Connect the electrode connectors
for the water flow for measurements and check that water flows through the valve.
5.
Open the faucets
for the water flow for measurements and check that water flows through the valve.
6.
Turn on the voltage
to Autodos M. After a startup time of 60 seconds, the values are shown in each respective channel/dis-
play, see section 9: Operation, page 13.
7.
Basic settings, electrodes
.
Autodos M has preset factory settings for all types of electrodes that normally corresponds to the electrode combination in
the supplied electrode kit. To check/change electrode type, see further under Systems configuration, pages 21-26.
8.
Basic settings, dosage type
.
Autodos M can control the dosage equipment either via on/off- frequency- , pulse width- or current control. Which to choose
depends on what dosage product that shall be connected. To check or change dosage type, see further for the specific mod
-
els under Electrode specific configuration, pages 26-29.
9.
Adjust the flow of water for measurement
to 30-40 liters/hour with the adjustment screw on the start module. Press the
button ↑
Flow
[9] and keep pushing and the current flow is shown in the right display.
10.
Calibrate electrodes,
see section 10: Calibration, pages 30-32.
11.
Let Autodos M run without dosage for around one hour with correct flow of water after the calibration have been done. This is
because the electrodes need to adjust to the measuring water in order for the signals to be stable. Read more under section
9: Handling/choice of dosage, page 15. Normal operating mode: diode “
Auto
” is lit.
12. Dosage times and response times depends solely on pool volume, turnaround ratio, dosage type, and dosage ratio.
Concentrations of chemicals and dosage products also affects. See section 9: Handling/Settings recommended values,
pages 17-18.
13.
Alarm; diodes with flashing lights show active or retset alarms. Pushing the button
Reset
[15] will shows the type of alarm.
Diodes with a steady red light are acknowledged/active alarms, see section 9: Handling/Alarm diodes, page 20.
If diode “
Auto
” flashes on the chlorine/redox channel, the pH-value is outside the alarm limits and no dosage is done until
the pH-value is restored within given limits.
14. Maintenance and care; see section 11: Care, page 32. All reference measurements of water quality shall be done with a
digital photometric measuring tool. The measuring water shall always be taken from the draining faucet on Autodos M´s
prefilter unit.