Configuration - Autodos M1 chlorine
Line
Text
Setting
Explanation
-01
FLo
Selection of flow switch and alarm for low flow.
oFF
No flow switch. Flow alarm OFF.
Son
Flow switch that closes with flow. Flow alarm ON.
Pof
Turbine flow meter. Flow alarm OFF.
Pon*
Turbine flow meter. Flow alarm ON.
-02
FCL
Selection of electrode type for chlorine measurement.
Pb*
PB200 or CLE2.2
Cur
4–20mA sensor e.g. CLE3
-03
PC
Setting of access from PC.
No*
No access (display only).
rES
Alarm reset only.
Prg
Fully programmable.
-04
Sio
001-255 (001*)
Selection of Modbus ID number
-05
FLd
000-030 (000*) [minutes]
Flow alarm delay time.
-06
rEL
000-030 (000*) [minutes]
Alarm relay delay time.
-07
SbY
The SbY input blocks all dosing plus the alarm relay.
rEL*
Activates the alarm.
non
Does not activate the alarm.
* Factory default!
Configuration - Autodos M1 redox
Line
Text
Setting
Explanation
-01
FLo
Selection of flow switch and alarm for low flow.
oFF
No flow switch. Flow alarm OFF.
Son
Flow switch that closes with flow. Flow alarm ON.
Pof
Turbine flow meter. Flow alarm OFF
Pon*
Turbine flow meter. Flow alarm ON.
-02
PC
Setting of access from PC.
No*
No access (display only).
rES
Alarm reset only.
Prg
Fully programmable.
-03
Sio
001-255 (001*)
Selection of Modbus ID number
-04
FLd
000-030 (000*) [minutes]
Flow alarm delay time.
-05
rEL
000-030 (000*) [minutes]
Alarm relay delay time.
-06
Sby
The Sby input blocks all dosing relays.
Also select whether it should activate the alarm relay.
rEL*
Activates the alarm.
non
Does not activate the alarm.
* Factory default!