Electrode-specific configuration - free chlorine/redox (PB200, CLE 3, Jesco, Redox)
For configuration of free chlorine electrodes.
Autodos M3 model - Free chlorine, redox, pH
:
press the buttons
Set alk/Cl
[13] +
Select function
[1].
For all other models:
press the buttons
Set value
[13] +
Select function
.
This is indicated via the text “
SEt FCL
” and flashing of the “
Off
” and “
Auto
”
LEDs
.
To exit configuration, press the
Cal.
button [0] or scroll past the last line.
Autodos M2 and M3
Select the desired line with the ↑ or ↓ button under the relevant display.
While the ↑ or ↓ button is depressed, display 2 shows the selected configuration type (e.g. “
FCL
” “
-01
”) and display 3 shows
the actual line number.
When the button is released, display 2 shows a text indicating which setting can be changed and display 3 shows a text or a
numeric value.
To change a text or value, press ↑ or ↓ under the relevant display.
The selected configuration is indicated via one of the following texts: “
SEt
”, “
FCL
”, “
CCL
”, “
ACi
” or “
bAS
”.
Autodos M1
Select the line for which you want to change the setting by pressing the
Alarm high
[12] or
Alarm low
[14] button.
When the
Alarm high
[12] or
Alarm low
[14] button is held depressed, the display shows the actual line number.
When the button is released, the display shows either a text or a numeric value. To change a text or value, press ↓ or ↑ .
The selected configuration is indicated via one of the following texts:: “
SEt
”, ”
FCL
”, ”
ACi
” or ”
bAS
” depending on type.
The following can be modified in the channel-specific configuration – Free chlorine:
Line
Text
Setting
Explanation
-01
doS
Selection of dosing outlet and function.
oFF
No dosing.
ono*
On-/Off-dosing.
Pdo
Pulse width dosing..
FrE
Frequency dosing..
Cur
Dosing via current output..
-02
P
0.10–2.00 (0,20*) ppm
P-band. (Pdo, FrE, Cur)
-03
I
000–100 (000*)
minutes
I-time, 000 = no I-regulation. (Pdo, FrE, Cur)
-04
d
000–100 (000*)
seconds
D-tid, 000 = no D-regulation. (Pdo, FrE, Cur)
-05
dF
010–180 (100*)
strokes/minute
Max. frequency dosing. (FrE)
-06
Pdo
005–015 (010*)
minutes
Pulse width during pulse width dosing. (Pdo)
-07
Ldt
000–060 (000*)
minutes
Long dosing time alarm, 0 = no function.
-08
oFt
000–600
seconds
Min. time OFF for relay, 0 = no function. (ono)
-09
ont
000-600
seconds
Min. time ON for relay, 0 = no function. (ono)
-10
Cur
- - 0 / - - 4 (- - 4*)
Current output, selection of range 0–20mA / 4–20mA.
-11
C-L
0.00–9.99 (0.00*) ppm
Current output, value for 0/4mA.
-12
C-H
0.00–9.99 (5.00*) ppm
Current output, value for 20mA.
-13
AHd
005–600 (005*) seconds
Delay time for high alarm.
-14
ALd
005–600 (005*) seconds
Delay time for low alarm.
* Factory default!