15
ENGLISH
Autodos M
MA60-10E
ENGLISH
Autodos M
MA60-10E
Showing other information on the display
Show
Uncalibrated
values
Press and hold the
Set value
[13] (or
Set Alk/Cl
[13]) and
Alarm low
[14] buttons simultaneously to show
uncalibrated values on the relevant display.
Show
Flow
Press and hold the ↑
Flow
button [9] to display flow in litres per hour.
Show
Temperature
Press and hold the ↓
Temp
button [8] to display temperature (in °C).
Show
Version
Press and hold the
Alarm high
[12] and
Alarm low
[14] buttons simultaneously to display the program
version.
Show
Serial number
Press and hold the
Function
[11] (or
Set Acid
[11]) and
Alarm high
[12] buttons simultaneously to display
the factory-programmed serial number.
Dosing selection
Select
Function
Press the
Select function
button [1], [4] or [7] to switch dosing selection between Off and Auto.
Dosing can be deselected in configuration mode.
To access manual dosing: press and hold the
Select function
button depressed, then press
Set value
[13]
button also. (The
Set value
button [13] is called
Set alk/Cl
[13] on M3 with redox.)
Deactivate manual dosing by pressing the
Select function
button.
Off
No dosing
Auto
Automatic dosing based on set parameters (normal setting)
Dosing
Indicates dosing (including when there is an error; stopped if there is a dosing time error)
Other buttons
Reset
Press and hold the
Reset
button [15] to display triggered alarms for the respective channel in the form of a
brief text. If the button is depressed for less than about one second, the alarms are reset and the common
alarm relay is de-energized. The dosing time counter is always zeroed with a reset.
Cal.
Press the
Cal.
button [0] to page in calibration mode between Off – Active – Adjust ...
This is indicated via unlit LEDs (Off), illuminated Active LED or illuminated Active and Adjust LEDs.
(Exit calibration mode by pressing and holding
Cal.
[0] until the LEDs go out.)
↑ ↓
Use the arrow buttons to adjust set values, limits and calibration values on the relevant display.
If an arrow button is held in, a “fast forward” function engages after about one second.
LEDs – dosing indicators
Off
Dosing of pH-regulating or chlorine-regulating agent is deactivated.
Auto
Dosing of pH-regulating or chlorine-regulating agent is regulated automatically.
Dosing
Dosing of pH-regulating or chlorine-regulating agent is in progress.
If neither LED “
Off
” nor “
Auto
” is illuminated, then manual dosing is selected. If dosing does not occur at this time (the LED
“
Dosing
” is not lit), then dosing was deselected at setup. It may also be deactivated due to excessively long dosing time if this
function has been selected. If this is the case the “
Alarm
” LED will flash also (or be illuminated).
If the pH value is outside of alarm limits, there is an alarm on the chlorine channel if chlorine dosing is active.
Chlorine dosing is stopped until the pH values are once again within permitted limits.
The alarm is indicated via a flashing “
Auto
” LED on the chlorine channel and the alarm test “
PHF
” at Reset..
LEDs – alarm indicators
Low flow
Insufficient flow in the flow cell.
Alarm
High alarm, low alarm, dosing error or flow error.
If the “
Alarm
” LED flashes, there is an error that has not been cleared. If an error has been cleared but remains active, the LED
is illuminated with a steady glow.