5 Timing charts
-
37
-
5.7 Alarm
clear
●
C
●
D
The figure below shows an example of how the signals behave when a LS detection error occurs.
ON
OFF
ON
OFF
ON
OFF
+LS input
ACL input
ALM output
Motor excitation
4 ms or more
100 ms or more
200 ms or less
10 ms or less
6 ms or less
6 ms or less
5.8 Reading current position data
●
C
●
D
REQ input
CK input
OUTR output
5 ms or less
1
2, 3
4
OUT0 output
OUT1 output
Once
Twice
Twentyeight
times
OFF
ON
OFF
ON
OFF
ON
OFF
ON
1.
Turn the REQ input ON.
2.
When the OUTR output turns ON, turn the CK input ON.
When the OUTR output turns OFF, save the statuses of OUT0 and OUT1 outputs to the host controller.
3.
Turn the CK input OFF.
Repeat steps 2 and 3 above 28 times.
4.
Turn the REQ input OFF.
The information effective at the time the REQ input turned ON is read.
Turning the REQ input OFF while information is being read will cancel the reading of current position data.
I/O Used for reading current position data
Signal name
Description
REQ input
This signal turns ON while data is being read.
CK input
This signal is used to request data (clock).
OUTR output
This signal turns ON when the CK input is OFF and the controller is ready to output
the OUT0 and OUT1 outputs.
This signal turns OFF when the CK input is ON and the controller has completed
outputting the OUT0 and OUT1 outputs.
OUT0 output
OUT1 output
These signals represent two data bits. The OUT0 output represents the lower bit,
while the OUT1 output represents the upper bit.
Data is output by 2 bits at a time from the most significant bit every time the CK
input turns ON.