Replace the Power Supply Backplane Board (FRU)
208
Sun Server X4-4 Service Manual • October 2015
23.
Connect the ribbon cable from the motherboard to the power supply backplane.
24.
Replace the power supply cover and fasten it in place with the screw.
25.
Connect the data and power cables from the fan board to the motherboard.
26.
Connect the disk drive backplane power cable and ribbon data cable.
27.
To install the air divider:
Note -
The air divider contains the Fault Remind button mechanism. To ensure that the
mechanism can engage the motherboard-mounted switch, the divider
must
be installed
correctly.
a.
Align the two tabs on the divider with the two slots in the power supply side
wall.
Содержание Sun Server X4-4
Страница 1: ...Part No E38221 05 October 2015 Sun Server X4 4 Service Manual ...
Страница 2: ......
Страница 10: ...10 Sun Server X4 4 Service Manual October 2015 ...
Страница 14: ...14 Sun Server X4 4 Service Manual October 2015 ...
Страница 16: ...16 Sun Server X4 4 Service Manual October 2015 ...
Страница 64: ...64 Sun Server X4 4 Service Manual October 2015 ...
Страница 88: ...88 Sun Server X4 4 Service Manual October 2015 ...
Страница 123: ...Remove a Power Supply Servicing CRU Components 123 3 Disconnect the power cord from the failed power supply ...
Страница 280: ...280 Sun Server X4 4 Service Manual October 2015 ...
Страница 284: ...284 Sun Server X4 4 Service Manual October 2015 ...
Страница 292: ...292 Sun Server X4 4 Service Manual October 2015 ...