38
Explicit Message Communications
Section 2-6
Write Timer Setting
Writes the timer setting for the OFF-delay, ON-delay, or one-shot timer of the
Sensor for the unit number specified in the instance ID. The data is given as a
2-byte (4-digit) hexadecimal value. The value is set in ms. The setting range is
0000 Hex to 00C8 Hex, but the possible settings are restricted as follows:
An error will occur if a value is written that does not meet the above setting
interval conditions.
Write Hysteresis Width
Writes the hysteresis width of the Sensor for the unit number specified in the
instance ID. The data is given as a 2-byte (4-digit) hexadecimal value.
Write Custom Flags
Set whether the following settings for the Sensor of the unit number specified
in the instance ID can be set or monitored from the sensor key switch.
05
Flashing Setting:
0: OFF
1: ON
06
Sensing Setting:
0: Standard
2: Super long-distance
3: Super high-speed
07
08
Timer Mode:
1: OFF-delay
2: ON-delay
3: One-shot
09
10
Number of Display Digits:
0: 4 digits
1: 3 digits
2: 2 digits
3: 1 digit
4: 0 digits
11
12
13
Always 0.
14
Teaching during RUN
0: OFF
1: ON
15
Eco Mode
0: OFF
1: ON
Bit
Contents
Timer setting
Setting interval
0 to 20 ms
1-ms increments
20 to 200 ms
5-ms increments
Bit
Contents
00
Hold Setting:
0: Enable
1: Not displayed
2: Disable
01
02
Flashing Setting:
0: Enable
1: Not displayed
2: Disable
03
Содержание E3X-CIF11
Страница 3: ...iv...
Страница 21: ...10 Connecting Fiber Amplifier Units Section 1 3...
Страница 63: ...52 Setting Monitoring and Operating Sensors from the DeviceNet Configurator Section 2 7...
Страница 107: ...96 CompoWay F Message Communications Section 4 5...
Страница 125: ...114 Monitoring Incident Light Levels of E3X DA6 P Sensors Appendix B...
Страница 133: ...122 DeviceNet Connection Settings Appendix C...
Страница 135: ...124 DeviceNet Device Profile Appendix D...
Страница 137: ...126 Revision History...