DeviceNet Connection Settings
Appendix C
Step 3: Setting the Fiber Amplifier Sensor Communication Unit
1.
Set the number of bytes for each connection.
2.
Select the Fiber Amplifier Sensor Communication Unit to be set from the Configurator screen, and then click
the right mouse button.
3.
Select Property from the menu.
4.
Select the I/O Information Tab.
5.
Click the Edit Button.
6.
The following dialog box will be displayed. Set the connection and number of bytes to be used.
Example:
Bit-strobe: ON/OFF
data
COS:
Status data + incident light level data
When number of Sensors for incident light level monitoring is 16, settings for this example are
as follows:
Bit-strobe: 2
bytes
COS:
34 bytes (2 bytes
16 units + 2 bytes)
Note The above items will be returned to the default settings when the Configurator is restarted or a configu-
ration is uploaded. Therefore, errors may occur when operating the Configurator. Be sure to reset the
above items to prevent errors from occurring.