Operating Procedure for DeviceNet Communication Unit
Section 2-3
2-3
Operating Procedure for DeviceNet Communication Unit
Step
Item
Details
1
Mount the Communication Unit to
the DIN Track.
Mount the Unit to the DIN Track. After mounting the Fiber Amplifier Units to the
DIN Track, connect the Units to each other.
Note: To remove the Units from the DIN Track, first slide the Units apart to dis-
connect them, and then remove the Units from the DIN Track.
2
Connect the Fiber Amplifier Units
to the Communication Unit.
Connect the Communication Unit to the Fiber Amplifier Units by sliding the
Communication Unit until the clips on the end are aligned and a “click” sound
is heard.
3
Set the Sensors to RUN mode.
Set the mode switches to RUN mode.
4
Connect the DeviceNet communi-
cations connector.
Connect the DeviceNet Communications Connector.
Note: The DC power supply to the Communication Unit and all Fiber Amplifier
Units connected to it is supplied from the DeviceNet communications power
supply (V+, V–).
5
Set the rotary switches.
Two
upper
switches
Sets the DeviceNet node address (0 to 63).
Lower
switch
Sets the number of Sensors connected to the Unit (1 to 16).
(Enabled when DIP switch pin 3 is OFF only.)
Note 1: When DIP switch pin 3 is ON, set the number of Sensors
connected using the Configurator or explicit messages.
Note 2: Fiber Amplifier Units (E3X-DA6TW, E3X-DA8TW) that are
allocated two unit numbers must be counted as two Units
when counting the number of Sensors.
6
Set the DIP switch.
Pin 1
Pin 2
Operating mode setting
Number of Sensors
connected
OFF
OFF
Remote I/O communications
one-word mode
13 max.
ON
OFF
Remote I/O communications
two-word mode
16 max.
OFF
ON
Remote I/O communications
two-word mode with incident
light level monitoring
16 max.
Pin 3
Method for setting the number of Sensors.
OFF
Use the rotary switch to register setting.
ON
Use the Configurator or explicit messages to register settings.
7
Turn ON the DC power supply (V+,
V– DeviceNet communications
power supply).
Disconnect the E3X-MC11 Mobile Console before turning ON the DC power
supply.
8
Check the indicators.
MS
Operating normally when lit green.
NS
Operating normally when lit green
(DeviceNet online and communications connected).
SS
Communicating with Sensors when lit green.
9
Start communications.
Remote
I/O
Enable the scan list in the master and change the PLC to RUN
mode.
Explicit
mes-
sages
Send explicit messages from the master.
Содержание E3X-CIF11
Страница 3: ...iv...
Страница 21: ...10 Connecting Fiber Amplifier Units Section 1 3...
Страница 63: ...52 Setting Monitoring and Operating Sensors from the DeviceNet Configurator Section 2 7...
Страница 107: ...96 CompoWay F Message Communications Section 4 5...
Страница 125: ...114 Monitoring Incident Light Levels of E3X DA6 P Sensors Appendix B...
Страница 133: ...122 DeviceNet Connection Settings Appendix C...
Страница 135: ...124 DeviceNet Device Profile Appendix D...
Страница 137: ...126 Revision History...