22
DeviceNet Remote I/O Communications
Section 2-5
2-5
DeviceNet Remote I/O Communications
2-5-1
Master Word Allocations
The E3X-DRT21 data is stored in the IN Area of the DeviceNet master. Select
one of the following three operating modes using the DIP switch.
The DeviceNet Configurator can be used to set the connection type. The
Fiber Amplifier Sensor Communication Unit supports bit-strobe, polling, COS,
and cyclic connections. Refer to Appendix C DeviceNet Connection Settings
for details.
Remote I/O
Communications
One-word Mode
(Pins 1 and 2 OFF)
Up to 13 Sensors can be connected in this mode. One word is allocated to
each Sensor in the IN Area of the master. Fiber Amplifier Units are automati-
cally assigned unit numbers in ascending order starting from the Communica-
tion Unit (left side).
■
Mobile Console Communications Flag
Bit 13 turns ON when the Mobile Console is connected to the Communication
Unit. When the Mobile Console is connected, the DeviceNet Configurator or
explicit message communications cannot be used to perform setting and
monitoring operations.
■
Sensor Communications Error Flag
Bit 14 turns ON when the registered number of Sensors does not match the
number of Sensors that are enabled to communicate, or when a communica-
tions error occurs after communications have been established with the Sen-
sors.
Pin 1
Pin 2
Operating mode setting
Number of
Sensors
MODE0
MODE1
OFF
OFF
Remote I/O communications one-word mode
13 max.
ON
OFF
Remote I/O communications two-word mode
16 max.
OFF
ON
Remote I/O communications two-word mode
with incident light level monitoring
16 max.
ON
ON
Cannot be set.
---
Bit
Contents
00
Unit 1 ON/OFF data
01
Unit 2 ON/OFF data
02
Unit 3 ON/OFF data
03
Unit 4 ON/OFF data
04
Unit 5 ON/OFF data
05
Unit 6 ON/OFF data
06
Unit 7 ON/OFF data
07
Unit 8 ON/OFF data
08
Unit 9 ON/OFF data
09
Unit 10 ON/OFF data
10
Unit 11 ON/OFF data
11
Unit 12 ON/OFF data
12
Unit 13 ON/OFF data
13
Mobile Console Communications Flag
14
Sensor Communications Error Flag
15
Sensor Communications Flag
Содержание E3X-CIF11
Страница 3: ...iv...
Страница 21: ...10 Connecting Fiber Amplifier Units Section 1 3...
Страница 63: ...52 Setting Monitoring and Operating Sensors from the DeviceNet Configurator Section 2 7...
Страница 107: ...96 CompoWay F Message Communications Section 4 5...
Страница 125: ...114 Monitoring Incident Light Levels of E3X DA6 P Sensors Appendix B...
Страница 133: ...122 DeviceNet Connection Settings Appendix C...
Страница 135: ...124 DeviceNet Device Profile Appendix D...
Страница 137: ...126 Revision History...