3-21
3 Configuration Software
CJ-series PROFINET IO Controller Unit Operation Manual for NJ-series CPU Unit (W511)
3-3 PROFINET
IO C
ontroller DT
M
3
3-
3-3 C
onfig
uration
Additional Information
•
It is required for the PC to have an Ethernet connection to the Network to perform these oper-
ations.
•
Be sure to set the Device Name of the IO Device to exactly the same value as set in the IO
Controller’s IO Device setup sub-item.
Find Field
In the Find field a selection of the found IO devices can be made. The search string can be used
with wildcard characters (like *). The search is done on all fields of the Device Online list.
The Main item “Configuration” (see figure below) provides the following four sub-items:
•
CPU Setup
•
IO Controller Setup
•
IO Device Setup
•
IO Device Area
Control
Description
Search Devices
The
Search Devices
button initiates a scan of the network and shows all found
PROFINET IO Devices in the Network Scan View. For each device the MAC
Address, Device Type, the currently assigned name and IP Address are dis-
played. The PROFINET Name and the IP Address can be adjusted from
within this view.
Signal
When selecting
Signal
, the selected IO Device or IO Controllers will flash its
indicators for 3 seconds. This can be used to locate the IO Controller or IO
Device.
Set IP Address
An IP Address can be temporarily set to access the IO Device over TCP/IP
with a device-specific tool. When the IO Controller opens a connection to the
IO Device the IP Address is over written by the IP Address set in the IO Con-
troller’s configuration file.
The IP Address can also be set temporarily for the IO Controller, however this
can only be done when there is no configuration file in the IO Controller.
Set Device Name
The Device Name is used by the IO Controller to recognize the IO Device on
the network, to download parameters to the IO Device and initiate IO Data
communication. Setting the Device Name is mandatory.
According to the PROFINET specification the name may only contain lower
case characters, dashes and numbers. During entry of the Device Name the
characters entered are checked and corrected for possible illegal characters.
Reset to factory
defaults
The selected IO Device is reset to factory default settings. This normally
means no Name and no IP Address (0.0.0.0)
3-3-3
Configuration