This section briefly describes how to create, connect and configure the PROFINET IO network using
the CX-ConfiguratorFDT software and the Device DTM’s. More detail can be found in the following sec-
tions.
1
Select the Network Components (see section
2-3 Network Installation
) and build the network.
2
Connect the Personal Computer to the Ethernet network. Note that the PROFINET Scan Tool
(for assigning the IO Device names) can only operate when connected to the Ethernet network.
3
Start the CX-ConfiguratorFDT software and install the appropriate GSDML files and DTM’s for
the connected IO Devices.
4
Scan the PROFINET network with the PROFINET Scan View included in the CJ1W-PROFINET
IO Controller DTM. Give the detected IO Devices an appropriate name according to their posi-
tion and /or function. It is possible to give a IO Device a temporary IP-address but it will be
set/changed later by the IO Controller.
5
Add the PROFINET IO Controller as parent in the Network View. Configure the communication
parameters to connect to the IO Controller:
• Set an IP address in the PROFINET IO Controller by using the Network Scan View.
• Enter the same IP address in the DTM.
• Confirm the on-line connection by putting the DTM on-line.
• Set the PROFINET Names of the PROFINET IO Devices by using the Network Scan View.
6
Build up the network within CX-ConfiguratorFDT. Add the IO Devices to the Tree of the network
by dragging and dropping from the Device Catalogue. Assign the I/O modules for each individ-
ual IO Device. Use the exact names given to the IO Devices with the network scan tool. Make
sure that the IP address for each item on the network is unique.
7
Allocate the modules of the IO Devices to the intended CPU memory areas.
8
Download the configuration to the IO Controller.
9
Confirm proper operation by checking the Monitoring GUI of DTM and indicator status of the
Unit.
Additional Information
A common mistake when implementing IO Controller redundancy, is to download the same con-
figuration to both IO Controllers, thereby creating an IP address conflict as well as duplicating
the symbolic name. This should be avoided.
3-1-3
Establishing the PROFINET IO Network