6 Message Communications
6-8
CJ-series PROFINET IO Controller Unit Operation Manual for NJ-series CPU Unit (W511)
For the definition of the error codes for unsuccessful execution of CIP messages, refer to the
Smart-
Slice GRT1-Series GRT1-PNT PROFINET Communication Unit Operation Manual
(Cat No. W13E-
EN-
□□
).
If transmission of the message was unsuccessful, the response frame will only contain a response
code and no data block.
Response Codes
The table below lists the error codes for the explicit message.
Parameters
Send Destination Station Address (Command)
Specifies the station address of device to send the explicit message to over the PROFINET network.
Service Code (Command, Response)
The service code defines the action to be implemented with the data sent to the slave device, e.g.
Read, Write, Save. The service codes are listed in the Operation manual of the targeted slave
device.
For normal responses, the service code is returned within the response data block, with bit 15 of the
service code set to ON. For error responses, 94 hex, which indicates an error, is returned.
Class ID (Command)
Specifies the class ID for the explicit message destination. The supported Class ID values are spec-
ified in the Operation manual of the targeted slave device.
Response code
Error Name
Description
08FF
Service not supported
The service code is incorrect.
09FF
Invalid attribute value
The specified attribute value is not supported. The data written was
outside valid range.
16FF
Object does not exist
The specified instance ID is not supported.
15FF
Too much data
The data is larger than the specified size.
13FF
Not enough data
The data is smaller than the specified size.
0CFF
Object state conflict
The specified command cannot be executed due to an internal error.
20FF
Invalid parameter
The specified operation command data is not supported.
0EFF
Attribute not settable
An attribute ID supported only for reading has been executed for a
write service code.
10FF
Device state conflict
The specified command cannot be executed due to an internal error.
14FF
Attribute not supported
The specified attribute is not supported.
19FF
Store operation failure
The data cannot be stored in memory.
2AFF
Group 2 only server general
failure
The specified command or attribute is not supported or the attribute
was not set.
Command
code
28
01
No. of bytes
received
Error code
Response
code
Source station
address (local node)
Service code 94 (Hex)
00
00
94