1 Features and System Configuration
1-10
CJ-series PROFINET IO Controller Unit Operation Manual for NJ-series CPU Unit (W511)
1-3
CX-ConfiguratorFDT
The PROFINET IO Controller Unit requires a configuration before it can exchange data with IO
Devices. For this purpose OMRON provides the CX-ConfiguratorFDT Configuration program which
runs under Microsoft Windows™ NT 4.0, Windows™ 2000, Windows™ XP or Windows™ 7 operating
systems.
Together with CX-ConfiguratorFDT, OMRON provides DTM COM Objects for PROFINET IO Device
configuration.
CX-ConfiguratorFDT Container Application
CX-ConfiguratorFDT provides an FDT environment in which DTMs can be executed. The main func-
tion of CX-ConfiguratorFDT is to facilitate the DTMs and the data exchange between them. It pro-
vides the following functions.
•
Network setup functions: A tree view shows the relations between the DTMs, i.e. the relation
between the master and slave devices.
•
Device Catalogue functions: A Device Catalogue containing the installed DTMs is maintained,
to which the user can add new DTMs or delete them. Device DTMs can be added to the net-
work from this Catalogue.
•
Project maintenance functions: CX-ConfiguratorFDT provides the functions to create, save
and open project files. It facilitates user access control, which limits of use to authorized per-
sonnel only, using password protection.
CX-ConfiguratorFDT provides additional functions like printing, error logging, FDT Communication log-
ging and help files.
CJ1W-PNT21 PROFINET IO Controller DTM.
This DTM is used to configure the IO Controller to perform data exchange and to set up the memory
locations for the I/O data exchange. Furthermore, the DTM provides online diagnostics functions.
GRT1-PNT SmartSlice PROFINET IO Device DTM.
This DTM is used to configure the GRT1-PNT SmartSlice system. The type and number of units
inserted in the SmartSlice system can be configured. This defines the amount of I/O data that is
exchanged with the PROFINET IO Controller. All parameters of the SmartSlice buscoupler and the
separate SmartSlice units are directly accessible.
Additional Information
For more information on the GRT1-PNT DTM, refer to the SmartSlice GRT1-Series GRT1-PNT
PROFINET IO Communication Unit Operation Manual (Cat. No. W13E-EN-
□
).
Generic IO Device DTM
This DTM interprets standard PROFINET IO GSDML files. The DTM can only be used to configure
the I/O Data exchange between the PROFINET IO Controller and PROFINET IO Devices. The DTM
only contains very limited online diagnostics functions and online parameter setup is not possible.
Downloading the Configuration
After setting up the configuration, it must be downloaded to the PROFINET IO Controller Unit.
1-3-1
Overview
Содержание CJ1W-PNT21
Страница 3: ......
Страница 16: ...13 CJ series PROFINET IO Controller Unit Operation Manual for NJ series CPU Unit W511 ...
Страница 107: ...3 Configuration Software 3 36 CJ series PROFINET IO Controller Unit Operation Manual for NJ series CPU Unit W511 ...
Страница 198: ...Index 1 CJ series PROFIBUS Master Unit Operation Manual for NJ series CPU Unit W509 I Index ...