1-9
1 Features and System Configuration
CJ-series PROFINET IO Controller Unit Operation Manual for NJ-series CPU Unit (W511)
1-2 PROF
INET IO Co
ntro
ller Uni
t
1
1
-2-2
P
rotocol S
pecification
s
Setting section
Rotary Switches:
Unit No. (hexadecimal x 1), Two rotary switches (reserved)
Other functions
Error history size and storage of up to 80 error events including time
stamps in volatile memory. 16 error events can be logged into non-vola-
tile memory.
Current consumption
420mA at 5 VDC from the CPU power supply
External dimensions
31 x 90 x 65 mm (W x H x D)
Weight
100 grams (typical)
1-2-2
Protocol Specifications
Item
Specification
PROFINET Interface
Protocol
PROFINET IO
PROFINET unit type
PROFINET IO Controller
Isochronous mode
Not Available
Alarms
Alarm events from PROFINET IO
Devices are stored and can be for-
warded from the unit.
Transfer Specifications
Bitrate
100Mbps (100Base-TX)
Detection of transmission speed
Not automatic, fixed method is used.
PROFINET IO Cable
Type
LAN cable according to PROFINET
specification
Maximum transmission distance
100m (distance between nodes)
PROFINET Redundancy
Protocol
PROFINET IO Controller Redundancy
Configuration
DTM
Included in CX-ConfiguratorFDT
Item
Specification