![Omron CJ1W-PNT21 Скачать руководство пользователя страница 169](http://html.mh-extra.com/html/omron/cj1w-pnt21/cj1w-pnt21_operation-manuals_742351169.webp)
7 Troubleshooting and Maintenance
7-4
CJ-series PROFINET IO Controller Unit Operation Manual for NJ-series CPU Unit (W511)
Additional Information
If Module Status is Red lit or flashing then refer to the displayed error code on the 7- segment
display for further information.
Startup Errors
PROFINET Configuration Set Invalid
CPU Unit
Exchange
Bus error
Flashing (red) OFF
H0
000E
Unit number duplication
H1
---
CPU Unit faulty
H6
---
I/O table not registered
H7
---
CPU Unit service monitoring error
HE
0001
CPU Unit watchdog timer error
HF
0002
Unit Errors
Error log
(Hex)
Likely cause
Unit response
Device Variable Flag
Correction
---
During startup of the IO Con-
troller it encountered a problem
and can not continue.
The Unit will stop pro-
cessing. There will be no
error logged in the error
log.
None of the bits are set.
Restart the IO Controller.
Replace the IO Control-
ler if the error recurs.
IO Controller Functions
Error log
(Hex)
Likely cause
Unit response
Device Variable Flag
Correction
0202
During startup of the IO Con-
troller encountered a problem
interpreting the PROFINET IO
Configuration file. This could
be because the Unit started for
the first time and does not con-
tain a configuration file yet.
Also the Configuration file
could be damaged.
The Unit is started and is
capable to receive a
PROFINET Configura-
tion. It will not initiate
PROFINET IO Commu-
nication. Records the
error in the error log.
(IO Controller status 1)
*_ValidCfgSta
will be
FALSE.
Use CX-ConfiguratorFDT
to download a valid
PROFINET IO Configu-
ration in the IO Control-
ler
.
Replace the IO
Controller if the error
recurs.
Error category
Error
Indicators
Error log (Hex)
MS
NS
7-segment
Содержание CJ1W-PNT21
Страница 3: ......
Страница 16: ...13 CJ series PROFINET IO Controller Unit Operation Manual for NJ series CPU Unit W511 ...
Страница 107: ...3 Configuration Software 3 36 CJ series PROFINET IO Controller Unit Operation Manual for NJ series CPU Unit W511 ...
Страница 198: ...Index 1 CJ series PROFIBUS Master Unit Operation Manual for NJ series CPU Unit W509 I Index ...