After adding each of the IO Device DTMs to the network, configurations have to be selected for each of
them. Setting up a configuration involves:
• Selecting the proper I/O modules, which define the I/O data to be exchanged when operational.
• Setting up the device parameters, which will be send to the device to make or verify its settings.
All these settings will be downloaded to the IO Controller Unit, which will at startup send the data to the
individual IO Devices over the PROFINET IO network.
In order to define the I/O configuration, the DTM Configuration User Interface must be opened. To do
this, either
•
select the device in the Network view and double-click the left mouse button.
•
select the device in the Network view, right click the mouse and select
Configuration
from the
context menu.
•
select the device in the Network view, select Configuration from the Device menu.
The DTM will now open a device configuration window. This window can differ per DTM and is targeted
at the device to be configured. In this section the configuration through GSDML files with the PROFI-
NET IO Generic Device DTM is shown. For other DTMs refer to the documentation supplied by the ven-
dor of the DTM and device.
The figure below, shows the DTM User Interface for a GSDML file based device with PROFINET IO
Generic Device DTM.
Example
The DTM Configuration User Interface displays the following:
•
The selected modules for this device. Modules can be added through the
Add Module
but-
ton.
•
Details of the selected module. It is separated in I/O data and Parameters. If needed the
Parameters are settable. Which ones is defined in the GSDML file.
Adding/Inserting Modules
By pressing the
Add Module
button a Module is added to the end of the Module list.
The correct Module is select by a drop down list.
5-2-1
Defining the I/O Configuration
Содержание CJ1W-PNT21
Страница 3: ......
Страница 16: ...13 CJ series PROFINET IO Controller Unit Operation Manual for NJ series CPU Unit W511 ...
Страница 107: ...3 Configuration Software 3 36 CJ series PROFINET IO Controller Unit Operation Manual for NJ series CPU Unit W511 ...
Страница 198: ...Index 1 CJ series PROFIBUS Master Unit Operation Manual for NJ series CPU Unit W509 I Index ...