Firmware Upgrade
In the rare occasion a firmware upgrade is needed for the CJ1W-PNT21 PROFINET IO Controller this
can be done in the Firmware Upgrade item. The IO Controller DTM must be set online to perform the
upgrade. The Current Firmware Version box shows the current firmware version of the IO Controller.
1
Click the
Browse
button and select the new firmware file from the standard Windows File Selec-
tion window.
2
When the firmware file is opened by clicking the
Open
button, it will be checked for consistency.
The new version number is shown in the Upgrade Firmware Version box.
3
The firmware upgrade process is started with the
Upgrade Now
button and the Progress is
shown in the progress bar.
4
When the firmware upgrade is completed, the new version can be read out by going online with
the CX-ConfiguratorFDT. The version will be visible in the Current Firmware Version. Detailed
information on the Firmware Upgrade process will be delivered with the new firmware file.
Precautions for Correct Use
Precautions for Correct Use
Do not turn off the power to the IO Controller during firmware upgrade. This may cause fatal and
irreversible damage to the IO Controller. Always follow the directions supplied with the firmware
file for upgrading the IO Controller Unit.