5-21
5 Operation
CJ-series PROFINET IO Controller Unit Operation Manual for NJ-series CPU Unit (W511)
5
-3 Co
nf
igurin
g t
h
e IO
Co
ntro
ller
5
5-
3-6 Suppo
rted Da
ta T
ypes a
nd Conversion
The CJ1W-PNT21 PROFINET IO Controller Units perform an interface function between a PROFI-
NET IO network and the NJ CPU. On both sides of the interface different formats for data and data
storage are used.
To ensure that I/O data transferred through the interface can be used on both sides of the interface
without additional formatting, the CJ1W-PNT21 PROFINET IO Controller Units perform the neces-
sary data formatting. This ensures that I/O data in the CPU memory can be processed by standard
CPU Instructions and that the I/O data transferred to / from the PROFINET IO Devices over the net-
work is compliant with the PROFINET IO definitions.
Precautions for Safe Use
PROFINET IO Data types may not match the NJ-series Controller data types.
The table below lists the I/O data formats supported by both the PROFINET IO network and CPU.
5-3-6
Supported Data Types and Conversion
Data Type
Size
[bytes]
PROFINET IO
NJ-series Controller
Boolean
1
Supported.
Data is transmitted on a byte-by-byte
basis.
Supported
Single 16-bit integers are trans-
ferred to memory words in CPU
memory.
Single 8-bit Integer
signed/unsigned
1
Supported.
Data is transmitted on a byte-by-byte
basis.
Supported
Minimum is 16-bit words. Two
bytes will be formatted in one
word. Words containing odd bytes
will be padded with zeros.
Single 16-bit Integer
signed/unsigned
2
Supported.
Data is transmitted on a Most-Signifi-
cant-Byte First basis.
Supported.
Single 16-bit integers are trans-
ferred to memory words in CPU
memory.
Single 32-bit Integer
signed/unsigned
4
Supported.
Data is transmitted on a Most-Signifi-
cant-Byte First basis.
Supported.
Data is stored with the Least-Sig-
nificant-Word at the lowest
address.
Single 64-bit Integer
signed/unsigned
8
Supported
Data is transmitted on a Most-Signifi-
cant- Byte First basis
Supported
Single 16-bit integers are trans-
ferred to memory words in CPU
memory.
32-bit Floating point
4
Supported.
Data is transmitted on a Most-Signifi-
cant-Byte First basis.
Supported.
Data is stored with the Least-Sig-
nificant-Word at the lowest
address.
64-bit Floating point
8
Supported
Data is transmitted on a Most-Signifi-
cant-Byte First basis
Supported
Single 16-bit integers are trans-
ferred to memory words in CPU
memory.
TimeOfDay
2
Supported
Data is transmitted on a Most-Signifi-
cant- Byte First basis
Supported
Single 16-bit integers are trans-
ferred to memory words in CPU
memory.
TimeOfDay with date indication
2
Supported
Data is transmitted on a Most-Signifi-
cant- Byte First basis
Supported
Single 16-bit integers are trans-
ferred to memory words in CPU
memory.