33
Peripheral Device Operations and Data Setting
Section 4-2
Setting the Bank Number
1,2,3...
1.
Monitor word n + 1 (the bank number).
Example: Shift
→
Word/Indirect
→
1
→
0
→
1
→
Monitor (When Unit no. is “0”)
2.
Write the present value to the bank that is to be executed.
Example: Change
→
1
→
Write (Bank no. = 1)
By means of either the Data Setting Console or the setting method using
a peripheral device which is described on the next page, set the data in ad-
vance in the bank that is to be executed.
When setting the number of the bank to be executed, make the setting with
bit 00 of word n OFF (i.e., with the Operation Flag OFF), or turn the Oper-
ation Flag OFF and then ON again after the setting has been made in word
n + 1.
Note The number of the bank to be executed can be set only in the operation mode.
Operation Startup
1,2,3...
1.
Monitor bit 00 of word n (the Operation Flag).
Example: Shift
→
Contact/Constant
→
1
→
0
→
0
→
0
→
0
→
Monitor (When Unit
no. is “0”)
2.
Press the Set/Reset Key to turn ON bit 00 of word n.
The following conditions will occur with operation startup:
The RUN indicator will light on the Data Setting Console.
Cam outputs will turn ON and OFF according to the cam ON/OFF data that
is set.
Bit 00 of word n + 8 (the in-Operation Flag) will turn ON.
Origin Adjustment
1,2,3...
1.
Turn ON bit 01 of word n (the Origin Adjustment Flag).
Example: Shift
→
Contact/Constant
→
1
→
0
→
0
→
0
→
1
→
Monitor
→
Set/Re-
set
2.
After the origin adjustment has been determined, write the value to EE-
PROM.
Turn ON bit 02 of word n (EEPROM write).
Example: Shift
→
Contact/Constant
→
1
→
0
→
0
→
0
→
2
→
Monitor
→
Set/Re-
set
Setting Cam ON/OFF Data
1,2,3...
1.
Write the DM usage conditions,described in (2) below, to DM m and DM m
+ 1.
2.
Write the bank number, cam number, and cam ON/OFF data to DM x on-
wards.
With the Programming Console, monitor each DM number and then write
the data by changing the present value.
For convenience, the Ladder Support Software (LSS) can be used.
The above settings can be be made after the operations described in (3),
but they must accord with the contents of (1).
3.
Either turn the Special I/O Restart Flag (AR 0100 to AR 0109) from OFF
to ON, or turn the C200H
power supply from ON to OFF and then ON
again.
These operations will cause the contents of (1) to be read.
Содержание C200H-CP114
Страница 1: ...23 5 7 21 0 18 Cat No W224 E1 2 SYSMAC C200H CP114 Cam Positioner Unit...
Страница 2: ......
Страница 3: ...C200H CP114 Cam Positioner Unit Operation Manual Revised January 2001...
Страница 4: ...iv...
Страница 6: ...vi...
Страница 8: ......
Страница 10: ......
Страница 59: ...45 SECTION 5 Troubleshooting This section provides possible errors and corrections Error Detection 46...
Страница 70: ......