
12
Wiring
Section 2-3
2-3-3
Data Setting Console Cables
Connecting Cable
Use the connecting cables in the table below (sold separately) to connect the
unit to the Data Setting Console.
Connection Precautions
Tighten the lock screws after inserting the connector into the unit.
Push the connector firmly into the Data Setting Console until the clips fully
lock.
Power is supplied from the Cam Positioner Unit via connection cable. If power
is not supplied between external cam output terminals (A10, B10) and (A9,
B9), the Data Setting Console cannot be operated.
Install the supplied connector cover when the cable is not connected.
Model
Cable length (L)
C200H-CN225
2 m
C200H-CN425
4 m
L
17.5
10
16.1
17.3
39
Содержание C200H-CP114
Страница 1: ...23 5 7 21 0 18 Cat No W224 E1 2 SYSMAC C200H CP114 Cam Positioner Unit...
Страница 2: ......
Страница 3: ...C200H CP114 Cam Positioner Unit Operation Manual Revised January 2001...
Страница 4: ...iv...
Страница 6: ...vi...
Страница 8: ......
Страница 10: ......
Страница 59: ...45 SECTION 5 Troubleshooting This section provides possible errors and corrections Error Detection 46...
Страница 70: ......