9
Wiring
Section 2-3
Note
1.
Do not connect the load directly until trial operation has been completed.
Instead, connect to a device that will enable monitoring the external cam
output status, such as a G7TC-OC16 I/O Relay Terminal.
2.
Be sure to supply power to terminals A10 and B10, or the Data Setting
Console will not operate. Power is supplied to the internal circuit and the
Data Setting Console via these terminals.
3.
Although there are internal connections between terminals A9 and B9, and
between A10 and B10, a wire must still be connected to each of these ter-
minals.
The following connector set manufactured by Fujitsu is included with the Unit:
FCN-361J024-AU (soldered connector)
FCN-360C024-J2 (cover)
Circuit Diagram
Recommended Cables
and Output Blocks
The following external cam output cables are recommended.
The following Output Blocks are recommended.
+V
OUT
COM
Inter
nal circuit
Model
Cable length
G79-100C
1 m
G79-150C
1.5 m
G79-200C
2 m
G79-300C
3 m
G79-500C
5 m
Model
Rated load
Relays used
Resistance load
Inductive load
G7TC-OC16
24 VDC 5 A,
220 VAC 2 A
24 VDC 2 A,
220 VAC 1 A
G7T-1112S
24 VDC
G7VC-OC16
24 VDC 2 A,
220 VAC 2 A
24 VDC 0.8 A,
220 VAC 0.8 A
G6B-1174P-FD-US
24 VDC
G7VC-OA16
75 to 264 VAC, 0.1 to 0.5 A
G3S-201PL-PD
24 VDC
G7VC-OD16
3 to 26 VDC, 0.01 to 0.5 A
G3SD-Z01P-PD
24 VDC
Содержание C200H-CP114
Страница 1: ...23 5 7 21 0 18 Cat No W224 E1 2 SYSMAC C200H CP114 Cam Positioner Unit...
Страница 2: ......
Страница 3: ...C200H CP114 Cam Positioner Unit Operation Manual Revised January 2001...
Страница 4: ...iv...
Страница 6: ...vi...
Страница 8: ......
Страница 10: ......
Страница 59: ...45 SECTION 5 Troubleshooting This section provides possible errors and corrections Error Detection 46...
Страница 70: ......