75
Setpoint Configuration Menu
22
22. SETPOINT CONFIGURATION MENU: (
SP.CNF
)
Setpoints 1 through 4 can be configured for a very large variety of zone and level signaling.
SP1 and SP2 have balanced configurable hysteresis and are non-latching, suitable for control-level
signaling.
SP3 and SP4 are often used as Alarm1 and Alarm2, because they have single-sided hysteresis and
can be configured for latching action.
The levels of these Setpoints are entered during run mode via the front-panel pushbuttons (refer to
Setpoint Settings Menu Configuration
Sections 8
) and many performance options are selected during
the configuration mode in the following sections.
SP.CNF
ENTER SETPOINT CONFIGURATION MENU:
Press ‘
MENU
’
1) Six times, display shows
"
SP.CNF
"
Setpoint Configuration Menu.
Press ‘
RESET/ENTER
’
2) Display flashes
"
dISAbL
"
(default) or previous selection.
Press ‘
䊱
/MAX
’
3) Select
"
ENAbLE
"
to configure Setpoint 1 and Setpoint 2.