background image

29

Signal and Power Input Connections

7

7.1 INTRODUCTION

The following describes how to connect your sensors to your meter with and without sensor ex ci ta tion

and how to connect the AC power to your meter. Prior to wiring the sensor to the meter, check with a

multimeter that a proper excitation exists.

WARNING:

Do not connect ac power to your meter until you have completed all input 

and output connections. Failure to do so may result in injury! This device must only be

installed electrically by specially trained electrician with corresponding qualifications.

Earth ground MUST be connected to the same earth ground used by the signal source, in

order to achieve published stability and accuracy specifications.

7.2 SIGNAL INPUT CONNECTIONS - PROCESS

The following 

Figures

(

7-1

through 

7-5

) show the connections for voltage, current and po ten ti om e ter

inputs:

Figure 7-1.  Current Input Without Sensor 

Figure 7-1.

Figure 7-1.  Current Input Without Sensor Excitation

Figure 7-2.  Current Input With Sensor 

Figure 7-2. Current

Figure 7-2.  Current Input With Sensor Excitation

NC

+S
–S

P9

1

2
3

1
2
3

P3

NC

+R

(+)

(

-

)

(4-20mA)

+E

–E

JUMPER

USER

PROVIDED

METER

-R

NC

+S
–S

P9

1

2
3

1
2
3

P3

NC
NC
NC

+

-

(4-20mA)

(+)

(

-

)

METER

Содержание DP41-B Series

Страница 1: ...DP41 B Universal Input Meter User sGuide omega com e mail info omega com For Latest Product Manuals omegamanual info Shop on line at RoHS 2 Compliant...

Страница 2: ...this document is believed to be correct but OMEGA Engineering Inc accepts no liability for any errors it contains and reserves the right to alter specifications without notice WARNING These products...

Страница 3: ...50 mV 0 100 mV Ranges 25 6 3 2 For 500 mV 0 1 V Range 25 6 3 3 For 5 V 0 10 V Ranges 25 6 3 4 For 50 V 0 100 V Ranges 26 6 4 Current Process Value Input 26 6 4 1 For 0 20 mA or 4 20 mA Range 26 6 5 B...

Страница 4: ...12 4 Input Type DC CURRENT 47 12 5 Input Type BRIDGE 48 12 6 Input Type POTENTIOMETER 49 SECTION 13 READING CONFIGURATION MENU and FLOWCHART 50 SECTION 14 READING CONFIGURATION MENU 14 1 Rd SC OF Ent...

Страница 5: ...ngs Display Menu 83 24 5 RSt AL Enter Alarm Reset Control Menu 83 SECTION 25 COMMUNICATION CONFIGURATION FLOWCHART 84 SECTION 26 COMMUNICATION MENU CONFIGURATION COMM 26 1 COM PAR Enter Communication...

Страница 6: ...1 3 Flashing ERR 02 Setpoint Overflow 104 32 1 4 NOSTOR STORED Programming Entries in EEPROM 104 32 1 5 Flashing OVLD Positive Input Overload 104 32 1 6 Flashing OPEN Open Sensor Indication 104 32 1...

Страница 7: ...7 7 Potentiometer Connections with External Power Supply and Ratio Measurement Remove Jumper S2 G 31 Figure 7 8 Directly Connected Thermocouple 31 Figure 7 9 Potentiometer Connections with 2 Wire RTD...

Страница 8: ...r Selection Table 28 Table 7 1 Thermocouple Wire Colors 37 Table 16 1 A D Analog to Digital Rate Option Table 60 Table 16 2 Factory Calculated Scale Factor Table 64 Table 18 1 Conversion Number Table...

Страница 9: ...ORTANT NOTE provides you with information that is important to successfully setup and use the Programmable Digital Meter CAUTION or WARNING tells you about the risk of electric shock CAUTION WARNING o...

Страница 10: ...Notes viii...

Страница 11: ...y setpoint Output options include Isolated programmable analog voltage or current and four relays With the Serial Communications option the user can select from a push button menu between RS 232 RS 48...

Страница 12: ...ommunications cable with phone plug termination Configuration Software and latest Operational Manual are available at the website listed in this manual Recommend purchase of 9SC2 or 25SC2 see OPTIONS...

Страница 13: ...am or configure the menu options along with the Jumper Settings Configuration accordingly For detail and illustration refer the Configuration Jumper Settings Section 6 This unit can be configured via...

Страница 14: ...g in transit Immediately report any damage to the shipping agent The shipping agent will not honor any claims unless all shipping material is saved for their examination After examining and removing c...

Страница 15: ...ocket Ribbon Connector P2 Connector 2 Panel Mounting Gaskets 1 Spare 1 Operator s Manual Other items may also be in the box depending on the options ordered Refer to specific options as described prev...

Страница 16: ...tch shall not be incorporated in the mains supply cord Furthermore to provide protection against excessive energy being drawn from the mains supply in case of a fault in the equipment an overcurrent p...

Страница 17: ...MAX MIN MENU RESET ITEM DESCRIPTION 1 or 6 digit 9 segment alphanumeric 0 68 high LED display with programmable decimal point 2 SETPOINT LED These LEDs labeled 1 through 4 display the status of setpoi...

Страница 18: ...ay In the Run Mode pressing the MAX button causes the display to flash the PEAK HI RdG Reading value press again to return to the Run Mode Press the MIN button to go back to a previous Level Menu item...

Страница 19: ...Top Level Menu item Press this button to store a submenu selection or after Entering a selected value state the display will flash a StOREd message to confirm your selection In Menu Configuration Mod...

Страница 20: ...1 1 1 1 1 1 1 1 1 P1 1 19 P1 AC POWER N C P1 DC POWER CONNECTOR DETAIL 1 TX TX RX N C N C RX N C N C 1 2 3 4 5 6 7 8 P4 ETHERNET N C RTN RX TX RTS N C N C N C RX TX RX TX 6 5 4 3 2 1 6 5 4 3 2 1 P4 R...

Страница 21: ...l I O Connector P3 Input Connector J4 Optional RS 232 RS 485 or Ethernet Connector P5 Optional Analog Output Connector P6 Optional Form C Relay 1 Connector P7 Optional Form C Relay 2 Connector P9 Inpu...

Страница 22: ...7 for wiring connection for power and sensor inputs In most cases if you have ordered optional boards with the meter these boards will already be installed You will need to remove only the rear cover...

Страница 23: ...oving boards this is as far as the unit needs to be disassembled Go to Section 5 2 1 2 Remove all wiring connectors from the rear of the unit 3 Remove the two thumbnuts that secure the case to the sle...

Страница 24: ...t the Main Board into the case once jumpers and optional boards have been configured and installed Spread the side panel detents of the case see Figure 5 2 and carefully slide the main board all the w...

Страница 25: ...ter s circuit boards Follow all instructions carefully BEFORE connecting the meter to any source of power DO NOT contact any exposed metal parts install optional board s change jumpers or in any way d...

Страница 26: ...gure 5 3 as a reference insert option board s into the corresponding connector s on the main board Each circuit board is keyed to fit in it s own position Figure 5 3 Optional Board Locations 4 RELAY O...

Страница 27: ...Reveal the main board refer to Section 5 2 Disassembly To access the S1 and S2 jumpers on the Signal Input Board you only need to remove the mounting sleeve 2 To re assemble the meter follow the steps...

Страница 28: ...stalled default MENU Pushbutton used for programming S3A not installed MENU Pushbutton only view settings but no store S3B not installed Factory Calibration only DO NOT install S3C installed Will skip...

Страница 29: ...S3 A OPEN CLOSE FOR TERMINAL RESISTOR S3 B OPEN CLOSE OPEN S3 C OPEN CLOSE FOR TERMINAL RESISTOR S3 D OPEN CLOSE OPEN S3 E OPEN OPEN CLOSE FOR RTS TRUE S4 CLOSE FOR OPEN CONTINUOUS MODE optional sele...

Страница 30: ...y 1 P6 A C A C Assigns SP2 to Relay 2 P7 Assigns SP3 to Relay 3 P18A Assigns SP4 to Relay 4 P18B Assigns SP1 to Relay 3 P18A B D A C Assigns SP2 to Relay 2 P7 Assigns SP3 to Relay 1 P6 Assigns SP4 to...

Страница 31: ...in board as well as those on any optional boards See Section 5 2 2 for main board jumper configuration and the appropriate sections for optional board jumper configuration 3 You have installed all opt...

Страница 32: ...e way into the panel cutout such that the gasket firmly backs the panel surface 9 Working from the rear of the panel slide the sleeve forward over the case and up to the panel surface The panel should...

Страница 33: ...ins 12 Replace the rear protective cover and secure it with the cover mounting screw Your meter is now ready for operation and you can turn on the power WARNING The unit becomes active as soon as it i...

Страница 34: ...B S2 S1 L K J H G F E D C A B 1 1 6 Jumper Settings 24 This section is for the configuration and setup of your jumper positions for readrate unipolar or bipolar signal input sensor input signal jumpe...

Страница 35: ...100mV ranges S1_K S2_A B G H jumpers are closed as shown NOTE For some applications the internal excitation is required install jumpers G and H on S2 as factory preset If the external excitation is us...

Страница 36: ...50mV 0 100mV ranges with Internal Excitation S1_L S2_A B G H jumpers are closed as shown S1 S2 6 5 2 For 50mV 0 100mV ranges with External Excitation S1_L S2_A B H jumpers are closed as shown S1 S2 6...

Страница 37: ...tation S1_L A B S2_G H jumpers are closed as shown S1 S2 6 5 8 For 50V 0 100V ranges with External Excitation S1_L A B S2_H jumpers are closed as shown S1 S2 6 5 9 For 0 20mA or 4 20mA range with Inte...

Страница 38: ...Jumper Function S4A installed solder jumper B Selects 10 Vdc Sensor Excitation default S4A not installed solder jumper A Selects 24 Vdc Sensor Excitation Table 6 1 Sensor Excitation Main Board Jumper...

Страница 39: ...ally by specially trained electrician with corresponding qualifications Earth ground MUST be connected to the same earth ground used by the signal source in order to achieve published stability and ac...

Страница 40: ...ure 7 5 4 Wire Voltage Input With Sensor Excitation R E S S E P9 P3 1 2 3 1 2 3 R JUMPER USER PROVIDED VOLTAGE EXCITATION OUTPUT EXCITATION OUTPUT METER NC R E S S E P9 P3 1 2 3 1 2 3 R JUMPER USER PR...

Страница 41: ...asurement Remove Jumper S2 G 7 3 SIGNAL INPUT CONNECTIONS TEMPERATURE The following Figures 7 8 through 7 11 show the connections for Thermocouple and RTD Inputs Figure 7 8 Directly Connected Thermoco...

Страница 42: ...D Connections with 2 wire RTD Figure 7 10 RTD Connections with 3 wire RTD Figure 7 11 RTD Connections with 4 wire RTD METER NC RTD E S S E R R P9 P3 1 2 3 1 2 3 NC METER NC RTD E S S E R P9 P3 1 2 3 1...

Страница 43: ...urrent Input Without Sensor Excitation rren Figure 7 13 Current Input With Sensor Excitation n Figure 7 14 Voltage Input Without Sensor Excitation rrent Input With Sensor Excitationge Input Without Se...

Страница 44: ...17 Bridge Input With External Sensor Excitation NC E S S E P9 P3 1 2 3 1 2 3 NC METER 50 mV NC E S S E P9 P3 1 2 3 1 2 3 GND VOLTAGE EXCITATION OUTPUT EXCITATION OUTPUT METER NC E S S E P9 P3 1 2 3 1...

Страница 45: ...o Measurement Figure 7 19 Potentiometer Connections with External Power Supply and Ratio Measurement Remove jumper S2 G R NC S S E P9 P3 1 2 3 1 2 3 GND JUMPER USER PROVIDED METER R E S S E P9 P3 1 2...

Страница 46: ...and P9 are identical and interchangeable connectors 3 Using a long slotted screwdriver one that is at least 4 long loosen the 6 screws on the connectors 4 Carefully install the thermocouple rear prot...

Страница 47: ...ive wiring designations are molded into the plastic cover Figure 7 21 Directly Connected Thermocouple 7 5 2 THERMOCOUPLE WIRE COLORS Table 7 1 Thermocouple Wire Colors USA T C WIRE COLORS TYPE LEAD _...

Страница 48: ...pleted all input and output connections Failure to do so may result in injury This device must only be installed electrically by specially trained electrician with corresponding qualifications The mai...

Страница 49: ...ied WARNING Do not connect dc power to your meter until you have completed all input and output connections Figure 7 23 DC Connector Wiring at P1 You are now ready to proceed with setting setpoints as...

Страница 50: ...yed for approximately 10 sec in the sequence of this Setpoint Setting Menu Flowchart unless the SETPTS is repeatedly pushed or setpoint is being edited SETPTS button SP4 RUN push 00000 0 00000 0 00000...

Страница 51: ...croll through available setpoints and return to RUN mode in the following sequence SP 1 Setpoint1 s value SP 2 SP2 s value SP 3 SP3 s value SP 4 SP4 s value RUN Press MAX 4 Enables the user to select...

Страница 52: ...t LCk CNF Menu AL CNF Run mode INPUT selection Menu READING CONFIGURATION Menu INPUT CONFIGURATION Menu MULTI POINT SCALE OFFSET CONFIGURATION Menu OUTPUT CONFIGURATION Menu SETPOINT CONFIGURATION Men...

Страница 53: ...43 Input Type Menu Flowchart 11 11 INPUT TYPE MENU FLOWCHART INPUt...

Страница 54: ...tep 6 tC stops flashing t C t C THERMOCOUPLE SUBMENU Press MAX 4 Scroll through the available selection to tC flashing Press RESET ENTER 5 Display shows tC again but not flashing Press RESET ENTER 6 D...

Страница 55: ...OREd stored message momentarily and then Rtd not flashing Press RESET ENTER 6 Display flashes previous RTD type selection ie 4Pt 385 default see Table below for types If the display matches your choic...

Страница 56: ...selection of voltage input type bI POL bipolar You must choose bi Polar or uni Polar before selecting Bridge or Potentiometer Press MAX 7 Scroll through the 2 available voltage input types to the sele...

Страница 57: ...ess MAX 4 Scroll through the available selection to CURRNt flashing Press RESET ENTER 5 Display shows CURRNt again but not flashing Press RESET ENTER 6 Display flashes 0 20MA current range default or...

Страница 58: ...E press RESET ENTER to skip to Step 6 bRIdGE stops flashing bRIdGE bRIdGE SUBMENU Press MAX 4 Scroll through the available selection to bRIdGE flashing Press RESET ENTER 5 Display shows bRIdGE again b...

Страница 59: ...press RESET ENTER to skip to Step 6 POt stops flashing POt POt POTENTIOMETER SUBMENU Press MAX 4 Scroll through the available selection to POt flashing Press RESET ENTER 5 Display shows POt again but...

Страница 60: ...1 value INPUt 2 Input 2 value REAd 2 Read 2 value CNt by Count By SEt dP Decimal Point Setting dP ACt V Decimal Point Active FILt tP Filter Type 001 002 005 010 020 050 100 FILt tM Filter Time A b C...

Страница 61: ...selection list Rd SC OF Reading Scale Offset Unt tMP Temperature Unit dEC Pt Decimal Point FILtER Reading Filters FLS dSP Flashing Display bRIGHt Display Brightness Option 14 1 Rd SC OF ENTER READING...

Страница 62: ...r 2 Cd INt 2 coordinate format for the configuration format of your choice If your choice of selection is 2 Cd INt skip to Step 17 dIRECt READING SCALE OFFSET DIRECT FORMAT MENU Direct scale and Offse...

Страница 63: ...L is to scale without known inputs Do this by calculating input values based on transducer specifications and manually entering them through the keyboard Press RESET ENTER 17 Display shows 2 Cd INt 2...

Страница 64: ...troller will also show the StOREd stored message momentarily MANUAL Press RESET ENTER 28 MANUAL heading stops flashing Press RESET ENTER 29 Display shows INPUt 1 Item 1 of coordinate 1 Pressing RESET...

Страница 65: ...nfirming that the decimal point position is active otherwise NO as independent Press MAX 7 To scroll or select the desired effect for your setting Press RESET ENTER 8 Display shows StOREd stored messa...

Страница 66: ...roller will also show StOREd stored message momentarily FILt tP Enter FILTER TYPE SELECTION MENU Press RESET ENTER 17 Display flashes A b C F IL Adaptive Bandwidth Control Filter Press MAX 18 Scroll t...

Страница 67: ...play Flashing or bRIGHt Display Brightness Control Menu If a change was made the controller will also show StOREd stored message momentarily 14 6 bRIGHt Enter DISPLAY BRIGHTNESS CONTROL SUBMENU Press...

Страница 68: ...N FRE Line Frequency Hz INP CNF Input Configuration INPUt 2 Input 2 value REAd 2 Read 2 value INPUt 2 Input 2 value REAd 2 Read 2 value SP1 L 2 H NORMAL DISAbL Offset 0 Scale 1 RAtIO Strain Ratio bRdG...

Страница 69: ...Input Scale Offset 16 1 L IN FRE Enter POWER LINE FREQUENCY SELECTION SUBMENU To enter POWER LINE FREQUENCY SELECTION Submenu if display shows L IN FRE Press RESET ENTER 4 Display shows flashing 60 i...

Страница 70: ...Rate Option Table Press RESET ENTER 9 Display advances to MOdE Input Mode Configuration Submenu If a change was made the controller will also show StOREd stored message momentarily 16 3 MOdE Enter INP...

Страница 71: ...nt automatically as described in the following steps Caution Before attempting to calibrate make sure you have the proper equipment for calibration and follow the procedure precisely The communication...

Страница 72: ...E or dISAbL for your choice of setup Press RESET ENTER 25 Display advances to IN SC OF Input Scale Offset Configuration Submenu or measurement setup menu If a change was made the controller will also...

Страница 73: ...lection and value entry for INPUt 1 and REAd 1 for INPUt 2 and REAd 2 item 1 and 2 of coordinate 2 similar to steps above Press RESET ENTER 39 Display advances to MP SC OF Multi Scale Offset configura...

Страница 74: ...al Range 0 50mV 0 100mV 0 1V 0 5V 1 5V 1 6V Scale Input 1 Value 000000 000000 000000 000000 010000 010000 Scale Input 2 Value 050000 100000 100000 050000 050000 060000 Input Signal Range 0 10V 0 50V 0...

Страница 75: ...SCALE OFFSET MENU CONFIGURATION FLOWCHART value value value value value MP SC OF NUM PNt OUt CNF INPUt0 REAd0 INPUt1 REAd1 INPUt0 REAd0 INPUt1 REAd1 INPUt9 REAd9 INPUt9 REAd9 0 10 value ON LINE MANUA...

Страница 76: ...d with 2 corresponding readings Up to 10 Linearization Points can be selected to customize the transducer curve MP SC OF Enter MULTI POINT SCALE OFFSET MENU Press MENU 1 Four times or scroll though Ma...

Страница 77: ...ess RESET ENTER 13 Display shows the 2nd higher live input signal being connected for your preference as equal to approximately 100 of the transducer range or the max Input signal Press RESET ENTER 14...

Страница 78: ...maximum of the transducer output range REAd 0 000000 REAd 1 000100 3 Scaling the controller Press RESET ENTER 18 Display stops flashing MANUAL Manual Scaling method menu Press RESET ENTER 19 Display...

Страница 79: ...READING VALUES READING INPUT SCALE OFFSET MODE y ax b MP SC OF IN SC OF Rd SC OF Yrd SCALE Xin OFFSET disable disable enable RS Xin RO disable enable disable IS Xin IO enable disable disable MS Xin M...

Страница 80: ...9 OUTPUT CONFIGURATION MENU FLOWCHART ANA OUt Analog Output OUt CNF ENAbLE MOdE dISAbL OUt tyP Output Type CURRNt VOLt FILtRd Filtered UNFILt Unfiltered PEAk VALLy Ot SC OF Output Scale Offset REAd 1...

Страница 81: ...OUt Analog Output Configuration submenu Press RESET ENTER 3 Display flashes dISAbL Default or previous setting option Press MAX 4 Select ENAbLE to setup Analog Output if your controller is equipped w...

Страница 82: ...tyP Enter OUTPUT TYPE CONFIGURATION SUBMENU Press RESET ENTER 7 Display shows OUt tyP Output Type Submenu Press RESET ENTER 8 Display flashes UNF ILt Unfiltered option or previous selection Press MAX...

Страница 83: ...ng 2 menu READING 2 Press RESET ENTER 17 Display flashes 1st digit of previous REAd 2 value Press MAX MIN 18 Enter REAd 2 value Example 999999 Press RESET ENTER 19 Display advances to OUt 2 Output 2 m...

Страница 84: ...ATION MENU FLOWCHART ENAbLE dISAbL SP CNF Setpoint Configuration N StAtE N OPEN ACt IVE AbOVE SP2 CNF N StAtE Normal State ACt IVE SP1 CNF N CLOSE bELOU AbOVE bELOU Below N OPEN Normal Open N CLOSE No...

Страница 85: ...d hysteresis and can be configured for latching action The levels of these Setpoints are entered during run mode via the front panel pushbuttons refer to Setpoint Settings Menu Configuration Sections...

Страница 86: ...t collector or Relay opened state or previous setting N CLOSE Normal Close Output Relay closed state Press MAX 10 Select your choice of Output Relay state setting Press RESET ENTER 11 Display shows St...

Страница 87: ...eviation LO dEV Low Deviation bNd dEV Band Deviation LAtCH ACtIVE N StAtE AL MOdE AL2 CNF Alarm 2 Configuration AbOVE LAtCH UNLtCH N CLOSE N OPEN bELOU Below PROC Process HI dEV High Deviation LO dEV...

Страница 88: ...ether the normal state of Output Collector or Relay is opened or closed with N StAtE submenu Following Alarm modes process no deviation high deviation low deviation and band deviation with AL MOdE sub...

Страница 89: ...ss MENU to enter the other available following submenu AL 2 CNF Alarm2 Configuration AL db Alarm Deadband Configuration NUM dLy Number of display reading configuration RSt AL Alarm Reset Submenu Refer...

Страница 90: ...TER button one time or by grounding connector P2 11 Reset can also be accomplished via RS 232 or RS 485 serial communication option board N StAtE Press RESET ENTER 11 Display shows StOREd stored messa...

Страница 91: ...ion Functions which can alter the alarm response as flowing illustrations All horizontal axes represent time line PROC Process Deviation No Deviation HI dEV High Deviation for both Active Above and Ac...

Страница 92: ...RATION MENU Press RESET ENTER 17 Display shows StOREd stored message momentarily and then advance to AL 2 CNF Alarm2 configuration submenu If necessary Press MENU to skip and enter the other available...

Страница 93: ...nter NUMBER OF READINGS DISPLAY MENU Press RESET ENTER 23 Display shows two 2 digit numbers 03 03 as default with the second right side of display one flashing Press MAX 24 To modify the delay value o...

Страница 94: ...face Standard RS 485 RS 232 MOdbUS COMM Communication dAt FMt Data String Format AL StAt Alarm Status Character P V Stat Peak Valley Status Character SNd dAt Current Reading Value Transmitted FL tRNS...

Страница 95: ...transformer with on board connector P11 Refer to Option Board Locations and Installation Section 5 2 2 Push Button Menu Configuration will be inaccessible during Serial Communication Main Communicati...

Страница 96: ...available following baud rate 000300 000600 001200 002400 004800 009600 and 019200 for your desired setting PARIty Press RESET ENTER 7 Display shows StOREd stored message momentarily and then advance...

Страница 97: ...nd out of the controller via the Serial Communication Bus Bus Format submenus essentially determine how and when data can be accessed via the Serial Communications of the device SUM CHk CheckSum NO yE...

Страница 98: ...r logging results on separate lines when displayed on communications software at a computer Press RESET ENTER 18 Display flashes NO No Line Feeds excluded option as default or previous selection Press...

Страница 99: ...programmed for a one meter bus This controller whether is setup with default RS 232 Serial Communication or not must be inspected visually for proper jumper configuration of Communication RS232 RS485...

Страница 100: ...k Hand Shake Method submenu Message Hand Shake The RTS Request To Send line from the host controller is checked when the device is ready to send measurement data If the RTS is true it sends the comple...

Страница 101: ...Format dAt FMt Data String Format AL StAt Alarm Status Character yES Included NO Excluded yES Included NO Excluded yES Included NO Excluded yES Included NO Excluded yES Included NO Excluded yES Includ...

Страница 102: ...nu The meter keeps track of Peak and Valley changes at the completion of each measurement so the occurrence of new values can be signaled However transmissions of Peak Valley status may be commanded l...

Страница 103: ...to the Pk tRNS Peak Value Transmission submenu that allows user to select whether Peak Value to be included or excluded in the Date String Press RESET ENTER 46 Display flashes NO No excluded as defau...

Страница 104: ...nt in Data String Format For detail and description of how to create your own units of measurement refer to Serial Communication Operation Manual Press RESET ENTER 55 Display flashes NO No excluded as...

Страница 105: ...oice of setting This controller supports value within 000 199 26 6 SERCNt Enter SERIAL COUNT SUBMENU Press RESET ENTER 63 Display shows StOREd stored message momentarily and then advances to the SERCN...

Страница 106: ...Y COLOR SELECTION MENU FLOWCHART N COLOR Normal Color SP1 CLR Setpoint 1 Color SP2 CLR Setpoint 2 Color AL1 CLR Alarm 1 Color AL2 CLR Alarm 2 Color COLOR GREEN REd AMbER GREEN REd AMbER HOLd GREEN REd...

Страница 107: ...nus allow the user to change the color of display when setpoint is reached or alarm is triggered 28 2 SP1 CLR Enter SETPOINT 1 COLOR SUBMENU Press RESET ENTER 5 Display shows StOREd stored momentarily...

Страница 108: ...ID code ERROR RUN SP1 SP2 ENAbLE dISAbL ENAbLE dISAbL Id INPUt RdG CNF ENAbLE dISAbL INP CNF MP SC OF OUt CNF SP CNF AL CNF COMM COLOR LOCk 3 times NO YES ENd RUN ENAbLE dISAbL ENAbLE dISAbL ENAbLE dI...

Страница 109: ...rity ID menu Press RESET ENTER 3 Display shows 4 numbers 0 0000 with the first digit flashing Press MAX MIN 4 To enter Access Security ID code The default code is any 4 digit number that has the sum o...

Страница 110: ...roll and select ENAbLE to lockout SP1 Setpoint 1 from any unauthorized modification or skip this menu just Press RESET ENTER Press RESET ENTER 12 Display shows StOREd stored message momentarily and th...

Страница 111: ...when P2 1 and P2 4 are connected to a momentary contact switch This feature allows you to automatically zero your meter when the switch is activated Tare is not available for temperature meters 31 2...

Страница 112: ...ices but isolation should be provided if there is a possibility of common mode ground currents since this supply is NOT isolated from the signal input 31 9 DISPLAY HOLD PIN 9 Grounding this pin to P2...

Страница 113: ...llector of the first setpoint transistor can carry 150 mA 31 16 SP2 PIN 17 The open collector of the second setpoint transistor can carry 150 mA 31 17 AL1 PIN 18 The open collector of the third setpoi...

Страница 114: ...meter will only display 6 digits 999999 maximum 32 1 3 Flashing ERR 02 Setpoint Overflow After a Setpoint or Alarm value has been entered and then the ACTIVE decimal point has been moved one or more...

Страница 115: ...M OVF Unit Of Measure Overflow If a unit of measure is selected and you are near the full scale capability of the display and in the ACTIVE decimal mode the display will shift one digit to the left fo...

Страница 116: ...signal exceeds 6900 ohms Place the active decimal point all the way to the right side FFFFFF TO CORRECT Check both the input range and the actual input to find the error condition To correct either r...

Страница 117: ...le offset is not required because the input overscale message has higher priority than this message and would be displayed if there were an input overscale CB OVF POSSIBLE CAUSE CNT BY count by value...

Страница 118: ...58 to 3214 0 3 223 2 to 2041 2 0 2 B 100 to 1820 0 3 212 to 3300 0 3 373 2 to 2093 2 0 3 DINJ 200 to 900 0 6 328 to 1652 1 0 73 2 to 1173 2 0 6 for K type temperatures over 1250 deg C accuracy will be...

Страница 119: ...reading SPAN TEMPCO less than 20 ppm C WARMUP 55 minutes to rated accuracy It is recommended that the unit be continuously running to insure its accuracy CONVERSION TECHNIQUE Delta Sigma RESOLUTION 2...

Страница 120: ...to 340 Vdc DC equivalent 50 60 Hz 8 5 watts max IEC127 2 III 250 mA Time Lag or UL Slow Blow 10 to 32 Vdc 8 watts max See Approvals Section LINE VOLTAGE POWER VOLTAGES FREQUENCY POWER EXTERNAL FUSE P...

Страница 121: ...est with Command Mode Baud Rate at 19200 bps Command Mode Sample Rate Process 100mV Rate ms TC K type Rate ms Turn Around Time ms Turn Around Time ms 0 7 135 ms 7 135 ms 1 14 68 ms 14 68 ms 2 27 36 ms...

Страница 122: ...g and Panel Cutout SIDE VIEW SLEEVE CASE 1 89 48 0 70 17 8 5 23 132 8 PROTECTIVE COVER TOP VIEW 5 86 148 8 MAX 1 772 0 024 000 45 00 0 61 0 00 3 622 0 032 000 92 00 0 81 0 00 PANEL CUTOUT 0 25 6 4 MAX...

Страница 123: ...OPEN INPUT OUT OF RANGE NEGATIVE OPEN EXCESS INPUT SCALE OFFSET I OVSC EXCESS DISPLAY SCALE OFFSET R OVSC COUNT BY DISPLAY OVERFLOW 999999 DURING SETPOINT ADJUST RUN MODE OUT OF SELECTED DIGIT RANGE 9...

Страница 124: ...30 323 3019 150 39 7232 100 138 5055 370 236 7011 640 326 4768 140 43 8764 110 142 2925 380 240 1763 650 329 6401 130 48 0048 120 146 068 390 243 6399 660 332 7919 120 52 1098 130 149 8319 400 247 092...

Страница 125: ...4913 750 365 3907 60 75 9022 350 232 0651 760 368 4832 50 79 952 360 235 6271 770 371 564 40 83 9876 370 239 1774 780 374 6331 30 88 0096 380 242 7159 790 377 6904 20 92 0187 390 246 2427 800 380 736...

Страница 126: ...choose ENAbLE dIRECt UNt tMP C dEC Pt dP ACtV yES SEtdP FFFFFF FILtER CNtby 001 FILt tP A b C FIL FILt tM 016 FLS dSP SP1 FLS dISAbL SP2 FLS dISAbL AL1 FLS dISAbL AL2 FLS dISAbL bRIGHt H bRt INPUT CO...

Страница 127: ...AR BAUd 9600 PARIty Odd StOP 1bIT bUS FMt SUMCHk NO LN FEEd NO ECHO yES STNd RS 232 MOdE CMMNd HNd SHk MESSAG dAt FMt AL StAt NO P V StAt NO SNd dAt yES FL tRNS NO Pk tRNS NO VL tRNS NO SEPARA SPACE U...

Страница 128: ...If choose ENAbLE UNt tMP dEC Pt dP ACtV SEtdP FILtER CNtby FILt tP FILt tM FLS dSP SP1 FLS SP2 FLS AL1 FLS AL2 FLS bRIGHt INPUT CONFIGURATION INP CNF LIN FRE Ad RAtE MOdE If Choose tC tC CO JC C JUN...

Страница 129: ...CONFIG COMM COM PAR BAUd PARIty StOP bUS FMt SUMCHk LN FEEd ECHO STNd MOdE HNd SHk dAt FMt AL StAt P V StAt SNd dAt FL tRNS Pk tRNS VL tRNS SEPARA UNIt COMM continued MOdbUS AddRES SERCNt LED COLOR S...

Страница 130: ...asurements performed on circuits not directly connected to the Mains Supply power Maximum measuring voltages to Earth are 120Vdc This unit should not be used in Measurement Categories II III IV Transi...

Страница 131: ...ed to be used nor shall it be used 1 as a Basic Component under 10 CFR 21 NRC used in or with any nuclear installation or activity or 2 in medical applications or used on humans Should any Product s b...

Страница 132: ...city Indicators Turbine Paddlewheel Systems Totalizers Batch Controllers pH CONDUCTIVITY pH Electrodes Testers Accessories Benchtop Laboratory Meters Controllers Calibrators Simulators Pumps Industria...

Отзывы: