NOVUS AUTOMATION
32/48
144
Determines buzzer activation
RW
0
1
0
0
1
0
145
Setpoint High Alarm
RO
The limits depend on the psychrometric property configured
at address 133.
146
147
Setpoint Low Alarm
RO
The limits depend on the psychrometric property configured
at address 133.
148
Table 55
– Alarm ALM1 Output Registers
ALARM ALM2 OUTPUT REGISTERS
Address
Description
R/W
Min.
Max.
Default
Min.
Max.
Default
150
Variable that will set off alarm
RW
1
9
1
1
9
1
151
Type of alarm
RW
0
5
0
0
5
0
152
Alarm Setpoint High Input
RW
The limits depend on the psychrometric property configured
at address 150.
153
154
Alarm Setpoint Low Input
RW
The limits depend on the psychrometric property configured
at address 150.
155
156
Alarm blocking
RW
0
1
1
0
1
1
157
Alarm hysteresis
RW
0
200
0
0
200
0
158
Alarm ON time
RW
0
6500
0
0
6500
0
159
Alarm OFF time
RW
0
6500
0
0
6500
0
160
Determines the alarm status in case of
sensor error
RW
0
1
0
0
1
0
161
Determines buzzer activation
RW
0
1
0
0
1
0
162
Alarm Setpoint High
RO
The limits depend on the psychrometric property configured
at address 150.
163
164
Alarm Setpoint Low
RO
The limits depend on the psychrometric property configured
at address 150.
165
Table 56
– Alarm ALM2 Output Registers
ALARM ALM3 OUTPUT REGISTERS
Address
Description
R/W
Min.
Max.
Default
Min.
Max.
Default
167
Variable that will set off alarm
RW
1
9
1
1
9
1
168
Type of alarm
RW
0
5
0
0
5
0
169
Alarm Setpoint High Input
RW
The limits depend on the psychrometric property configured
at address 167.
170
171
Alarm Setpoint Low Input
RW
The limits depend on the psychrometric property configured
at address 167.
172
173
Alarm blocking
RW
0
1
1
0
1
1
174
Alarm hysteresis
RW
0
200
0
0
200
0
175
Alarm ON time
RW
0
6500
0
0
6500
0
176
Alarm OFF time
RW
0
6500
0
0
6500
0
177
Determines the alarm status in case of
sensor error
RW
0
1
0
0
1
0
178
Determines buzzer activation
RW
0
1
0
0
1
0
179
Alarm Setpoint High
RO
The limits depend on the psychrometric property configured
at address 167.
180
181
Alarm Setpoint Low
RO
The limits depend on the psychrometric property configured
at address 167.
182
Table 57
– Alarm ALM3 Output Registers