NOVUS AUTOMATION
39/48
11.3.3
OUTPUT PARAMETERS
By clicking on the icon
, you can configure the transmission analog outputs, the alarm outputs and the buzzer.
Fig. 33
– Output configuration screen
11.3.3.1
Configuring Transmission Outputs
To select the analog output to be configured, click once on the button for the analog output and enable it by sliding the enable key right.
Fig. 34
– Output 1
In the
Measurement
field, the psychrometric property to be transmitted by the analog output can be selected. The analog output
Mode
allows for
selecting the electrical standard to be used for transmission: 0-10 V or 4-20 mA. The electrical signal from the output will be proportional to the
selected variable, abiding by the values configured for
Lower Limit
and
Upper Limit
.
In case of sensor failure, the variable to be transmitted by the analog output will go into
Error Mode
. For this error condition, you can select
High
or
Low
status.
Error mode
Mode
Low
High
0 - 10 V
0 V
10 V
4 - 20 mA
3.6 mA
21.0 mA
Table 66
– Error mode