NOVUS AUTOMATION
17/48
7.2.1
Psychrometric property associated with alarms
ALM1
/
ALM2
It allows you to configure a psychrometric property that will be associated with alarms
ALM1
/
ALM2
.
ALm1
mEAs
ALm2
mEAs
Psychrometric property associated with alarms
ALM1
/
ALM2
Default:
t
Temperature
t
Relative humidity
r
k
Dew point temperature
Td
Wet bulb temperature
tW
Absolute humidity
du
Frost point temperature
Tf
Specific enthalpy
H
Partial vapor pressure
E
Mixture ratio
R
Table 10
– Psychrometric property associated with alarms
ALM1
/
ALM2
7.2.2
Activation mode for alarms
ALM1
/
ALM2
It allows you to turn off alarms
ALM1
/
ALM2
or configure them to operate as one of the alarm types indicated below:
ALm1
modE
ALm2
modE
Activation mode for alarm outputs
ALM1
/
ALM2
Default:
off
Off
oFF
Sets off alarm in case of sensor error
iErr
Sets off alarm below setpoint
SPLo
Lo
Sets off alarm above setpoint
SP
k
i
k
i
Sets off alarm between
SPLo
and
SP
k
i
L--k
Sets off alarm below
SPLo
and above
SP
k
i
-Lk-
Table 11
– Activation mode for alarm outputs
ALM1
/
ALM2
7.2.3
Lower Setpoint for activating alarms
ALM1
/
ALM2
It allows you to configure the set point for alarm types
Lo
,
L
--
k
and
-L
k
-
.
SI
US
ALm1
spLo
ALm2
spLo
Setpoint lower than alarm outputs
ALM1
/
ALM2
Min.
Max.
Unit
Default
Min.
Max.
Unit
Default
ALM1
/
ALM2
for temperature
-40
100
°C
-40
-40
212
°F
-40
ALM1
/
ALM2
for relative humidity
0
100
% RH
0
0
100
% RH
0
ALM1
/
ALM2
for dew point temperature
-90
100
°C
-90 -130
212
°F
-130
ALM1
/
ALM2
for wet bulb temperature
-40
100
°C
-40
-40
212
°F
-40
ALM1
/
ALM2
for absolute humidity
0
600
g/m³
0
0
262
gr/ft³
0
ALM1
/
ALM2
for frost point temperature
-90
100
°C
-90 -130
212
°F
-130
ALM1
/
ALM2
for specific enthalpy
-40 700000
*
kJ/kg
-40
-18 300945
*
BTU/lb
-18
ALM1
/
ALM2
for partial vapor pressure
0
1035
Mbar
0
0
15
psi
0
ALM1
/
ALM2
for mixture ratio
0 260000
*
g/kg
0
0 1820000
*
gr/lb
0
Table 12
– Setpoint lower than alarm outputs
ALM1
/
ALM2
*
These values extrapolate the maximum value that can be shown by the display. Using the HMI, you can set up to the limit of 19999. When configured via
NXperience
, these parameters
can be adjusted up to the values shown on the table above, but when accessing these parameters via the HMI, they will display the value
nnnn
.