NOVUS AUTOMATION
24/48
7.6
COMMUNICATION CYCLE
In the communication cycle, you will find configuration parameters for the RS485 Modbus serial port: Baud rate, parity and address.
7.6.1
Baud Rate
The
RHT Transmitter
can be access via a Modbus-RTU network. The baud rate, parity and device address on the network need to be configured
for this. The device responds to the read and write commands in its internal registers according to the specifications set out in this manual (see
chapter on SERIAL COMMUNICATION).
[
nfG
BAud
Baud Rate
19.2
1200 bps
1.2
2400 bps
2.4
4800 bps
4.8
9600 bps
9.6
19200 bps
19.2
38400 bps
38.4
57600 bps
57.6
115200 bps
115.2
Table 39
– Baud rate
7.6.2
Parity
This parameter configures the parity for
RHT
Climate
Transmitter
communication on a Modbus-RTU network.
[nfG
Prty
Parity
Default:
nonE
Without parity
nonE
Even Parity
EVEn
Odd Parity
Odd
Table 40
– Parity
7.6.3
Address
This parameter configures the address for
RHT
Climate
Transmitter
communication on a Modbus-RTU network. This parameter should be adjusted
so that no two devices use the same address within a Modbus-RTU network.
Min.
Max.
Unit
Default
[nfG
Addr
Internet address
1
247
-
1
Table 41
– Address