NOVUS AUTOMATION
30/48
10
SERIAL COMMUNICATION
The
RHT
Climate
Transmitter
can be recognized on an RS485 network with MODBUS RTU protocol as a slave device. All of the controller’s
configurable parameters can be read and/or written via serial communication. Writing to Registers in broadcast mode is also allowed, using address
0
.
The available Modbus commands are as follows:
03 – Read Holding Register
05 – Write Single Coil
06 – Write Single Register
16 – Write Multiple Registers
10.1
TABLE OF HOLDING REGISTER
TYPE REGISTERS
SI
US
PRIMARY CYCLE INDICATION REGISTERS
Address
Description
R/W
Min.
Max.
Default
Min.
Max.
Default
0
Relative humidity value
RO
0
10000
-
0
10000
-
1
2
Dry bulb temperature value
RO
-4000
10000
-
-4000
21200
-
3
4
Wet bulb temperature value
RO
-4000
10000
-
-4000
21200
-
5
6
Dew point value
RO
-9000
10000
-
-13000
21200
-
7
8
Frost point value
RO
-9000
10000
-
-13000
21200
-
9
10
Specific enthalpy value
RO
-4000
70000000
*
-
-1800
30094500
*
-
11
12
Absolute humidity value
RO
0
60000
-
0
26200
-
13
14
Partial vapor pressure value
RO
0
103500
-
0
1500
-
15
16
Mixture ratio value
RO
0
26000000
*
-
0
182000000
*
-
17
18
Minimum humidity value
RO
0
1000
-
0
1000
-
19
20
Maximum humidity value
RO
0
1000
-
0
1000
-
21
22
Minimum temperature value
RO
-4000
1000
-
-4000
2120
-
23
24
Maximum temperature value
RO
-4000
1000
-
-4000
2120
-
25
26
Minimum dew point value
RO
-9000
1000
-
-13000
2120
-
27
28
Maximum dew point value
RO
-9000
1000
-
-13000
2120
-
29
Table 51
– Primary cycle indication registers
*
For firmware version less than or equal to 1.10, the maximum enthalpy value is 32767 and the maximum mix ratio value is 65535.