7.1.3
Lower limit of the transmission range from analog outputs
0vt1
/
0vt2
It allows you to configure the lower background scale for analog outputs
0vt1
/
0vt2
.
SI
US
0vt1
L-Lo
0vt2
L-Lo
Lower limit of the transmission range from analog
outputs
0vt1
/
0vt2
Min.
Max.
Unit
Default
Min.
Max.
Unit Default
Temperature
t
-40
100
°C
-40
-40
212
°F
-40
Relative humidity
r
k
0
100
% RH
0
0
100
% RH
0
Dew point temperature
td
-90
100
°C
-90
-130
212
°F
-130
Wet bulb temperature
tW
-40
100
°C
-40
-40
212
°F
-40
Absolute humidity
du
0
600
g/m³
0
0
262
gr/ft³
0
Frost point temperature
tF
-90
100
°C
-90
-130
212
°F
-130
Specific enthalpy
h
-
40
700000
*
kJ/kg
-40
-18
300945
*
BTU/lb
-18
Partial vapor pressure
E
0
1035
mbar
0
0
15
psi
0
Mixture ratio
r
0
260000
*
g/kg
0
0
1820000
*
gr/lb
0
Table 06
– Lower limit of the transmission range from analog outputs
*
These values extrapolate the maximum value that can be shown by the display. Using the HMI, you can set up to the limit of 19999. When configured via
NXperience
, these parameters
can be adjusted up to the values shown on the table above, but when accessing these parameters via the HMI, they will display the value
nnnn
.
7.1.4
Upper limit of the transmission range from analog outputs
0vt1
/
0vt2
It allows you to configure the upper background scale for analog outputs
0vt1
/
0vt2
.
SI
US
0vt1
L-
k
i
0vt2
l-
k
i
Upper limit of the transmission range from
analog outputs
0vt1
/
0vt2
Min.
Max.
Unit
Default
Min.
Max.
Unit
Default
Temperature
-40
100
°C
100
-40
212
°F
212
Relative humidity
0
100
% RH
100
0
100
% RH
100
Dew point temperature
-90
100
°C
100
-130
212
°F
212
Wet bulb temperature
-40
100
°C
100
-40
212
°F
212
Absolute humidity
0
600
g/m³
600
0
262
gr/ft³
262
Frost point temperature
-90
100
°C
100
-130
212
°F
212
Specific enthalpy
-40 700000
*
kJ/kg
700000
*
-18 300945
*
BTU/lb
300945
*
Partial vapor pressure
0
1035
mbar
1035
0
15
psi
15
Mixture ratio
0
260000
*
g/kg
260000
*
0 1820000
*
gr/lb
1820000
*
Table 07
– Upper limit of the transmission range from analog outputs
*
These values extrapolate the maximum value that can be shown by the display. Using the HMI, you can set up to the limit of 19999. When configured via
NXperience
, these parameters
can be adjusted up to the values shown on the table above, but when accessing these parameters via the HMI, they will display the value
nnnn
.
7.1.5
Status of analog outputs
0vt1
/
0vt2
in case of sensor error
It allows you to configure the status of analog outputs
0vt1
/
0vt2
in case of error in the sensor reading.
0vt1
Err
0vt2
err
Value of analog outputs
0vt1
/
0vt2
in case of error
Default:
lo
Sets analog outputs
0vt1
/
0vt2
to the minimum value in case of error in the sensor reading.
lo
Sets the analog outputs
0vt1
/
0vt2
to the maximum value in case of error in the sensor reading.
X
i
Table 08
– Value of analog outputs
0vt1
/
0vt2
in case of error
7.2
ALARM OUTPUTS
ALM1
/
ALM2
All models of
RHT
Climate
Transmitters
have two alarm outputs, which can also be used with ON/OFF control outputs. For models with display,
there is the additional feature of an internal buzzer for audible signaling. For each alarm output and for the buzzer, the following can be configured:
•
The associated psychrometric property;
•
Alarm type
Lo
,
k
i
,
L
--
k
,
-
L
k
-
;
•
The setpoints;
•
Hysteresis;
•
Output condition in case of sensor error;
•
And the timing.