NOVUS AUTOMATION
19/48
7.2.8
Initial blocking of alarms
ALM1
/
ALM2
It allows blocking the activation of alarms
ALM1
/
ALM2
if the transmitter starts up in alarm condition.
ALm1
bLA
Alm2
bla
Initial blocking of alarms
ALM1
/
ALM2
Default:
yEs
Without initial blocking of alarms
ALM1
/
ALM2
no
With initial blocking of alarms
ALM1
/
ALM2
yEs
Table 17
– Initial blocking of alarms
ALM1
/
ALM2
7.2.9
Status of alarms
ALM1
/
ALM2
in case of sensor error
It allows you to configure the outputs from alarms
ALM1
/
ALM2
so that they are activated in case of sensor reading error.
ALm1
Err
Alm2
err
Status of alarm outputs
ALM1
/
ALM2
in case of sensor error
Default:
Off
Alarms
ALM1
/
ALM2
off
oFF
Alarms
ALM1
/
ALM2
on
On
Table 18
– Status of alarm outputs
ALM1
/
ALM2
in case of sensor error
7.2.10
Enable buzzer activation linked to alarms
ALM1
/
ALM2
It allows you to enable buzzer activation linked to alarms
ALM1
/
ALM2
.
ALm1
Bv22
Alm2
Bv22
Enable buzzer for alarm outputs
ALM1
/
ALM2
Default:
Dsbl
The buzzer will
not
be activated when alarms
ALM1
/
ALM2
occur.
Dsbl
The buzzer will be activated when alarms
ALM1
/
ALM2
occur.
Enbl
Table 19
– Enable buzzer for alarm outputs
ALM1
/
ALM2
7.3
BUZZER CONFIGURATION CYCLE
The buzzer configuration cycle allows for assigning the psychrometric property associated with the buzzer, the buzzer operating mode
(type of alarm), buzzer activation points, their timing values, inhibition of alarm condition when turning the device on, and the buzzer activation
mode in case of sensor reading error.
7.3.1
Psychrometric property associated with the buzzer
It allows you to configure the psychrometric property that will be associated with the buzzer.
Bv22
mEAs
Psychrometric property associated with the buzzer
Default:
t
Temperature
t
Relative humidity
r
k
Dew point temperature
Td
Wet bulb temperature
tW
Absolute humidity
du
Frost point temperature
Tf
Specific enthalpy
H
Partial vapor pressure
E
Mixture ratio
R
Table 20
– Psychrometric property associated with the buzzer
7.3.2
Buzzer activation mode
It allows you to turn off the buzzer or configure it to operate as one of the alarm types set forth below:
Bv22
modE
Buzzer activation mode
Default:
off
Off
oFF
Activates the alarm in case of sensor error
iErr
Activates alarm below setpoint
SPLo
Lo
Activates alarm above setpoint
SP
k
i
k
i
Activates alarm between
SPLo
and
SP
k
i
L--
k
Activates alarm below
SPLo
and above
SP
k
i
-L
k
-
Table 21
– Buzzer activation mode