NOVUS AUTOMATION
20/48
7.3.3
Lower psychrometric property setpoint for buzzer activation
It allows you to configure the setpoint for alarm types
Lo
,
L
--
X
and
-L
X
-
.
SI
US
Bv22
spLo
Psychrometric property
Min.
Max.
Unit Default Min.
Max.
Unit
Default
Temperature
-40
100
°C
-40 -40
212
°F
-40
Relative humidity
0
100
% RH
0
0
100
% RH
0
Dew point temperature
-90
100
°C
-90 -130
212
°F
-130
Wet bulb temperature
-40
100
°C
-40 -40
212
°F
-40
Absolute humidity
0
600
g/m³
0
0
262
gr/ft³
0
Frost point temperature
-90
100
°C
-90 -130
212
°F
-130
Specific enthalpy
-40 700000
*
kJ/kg
-40
-18 300945
*
BTU/lb
-18
Partial vapor pressure
0
1035
mbar
0
0
15
psi
0
Mixture ratio
0 260000
*
g/kg
0
0 1820000
*
gr/lb
0
Table 22
– Psychrometric property
*
These values extrapolate the maximum value that can be shown by the display. Using the HMI, you can set up to the limit of 19999. When configured via
NXperience
, these parameters
can be adjusted up to the values shown on the table above, but when accessing these parameters via the HMI, they will display the value
nnnn
.
7.3.4
Higher Setpoint for buzzer activation
It allows you to configure the set point for alarm types
k
i
,
L
--
k
and
-L
k
-
.
SI
US
Bv22
sp
k
i
Higher Setpoint for buzzer activation
Min.
Max.
Unit
Default
Min.
Max.
Unit
Default
Temperature
-40
100
°C
100
-40
212
°F
212
Relative humidity
0
100
% RH
100
0
100
% RH
100
Dew point temperature
-90
100
°C
100
-130
212
°F
212
Wet bulb temperature
-40
100
°C
100
-40
212
°F
212
Absolute humidity
0
600
g/m³
600
0
262
gr/ft³
262
Frost point temperature
-90
100
°C
100
-130
212
°F
212
Specific enthalpy
-40
700000
*
kJ/kg
700000
*
-18 300945
*
BTU/lb
300945
*
Partial vapor pressure
0
1035
mbar
1035
0
15
psi
15
Mixture ratio
0
260000
*
g/kg
260000
*
0
1820000
*
gr/lb
1820000
*
Table 23
– Higher Setpoint for buzzer activation
*
These values extrapolate the maximum value that can be shown by the display. Using the HMI, you can set up to the limit of 19999. When configured via
NXperience
, these parameters
can be adjusted up to the values shown on the table above, but when accessing these parameters via the HMI, they will display the value
nnnn
.
7.3.5
Hysteresis for turning off buzzer
It allows you to adjust the differential for turning off the buzzer.
SI
US
Bv22
k
yst
Hysteresis for turning off buzzer
Min.
Max.
Unit Default Min.
Max.
Unit
Default
Temperature
0
20
°C
0
0
20
°F
0
Relative humidity
0
20
% RH
0
0
20
% RH
0
Dew point temperature
0
20
°C
0
0
20
°F
0
Wet bulb temperature
0
20
°C
0
0
20
°F
0
Absolute humidity
0
20
g/m³
0
0
20
gr/ft³
0
Frost point temperature
0
20
°C
0
0
20
°F
0
Specific enthalpy
0
20
kJ/kg
0
0
20
BTU/lb
0
Partial vapor pressure
0
20
mbar
0
0
20
psi
0
Mixture ratio
0
20
g/kg
0
0
20
gr/lb
0
Table 24
– Hysteresis for turning off buzzer
7.3.6
Buzzer on time
Min.
Max.
Unit
Default