- 25 -
Symptom
Causes / Service Checks
On-off Switch Energized, Humidistat calling for
operation. Unit does not operate.
-
No power to appliance. Check circuit breaker. Check disconnect switch.
-
Defective Transformer. Check secondary voltage. If no 24 volts, replace
transformer if breaker is not blown.
-
Check re-setable stack high limit switch and reset if necessary.
-
Low voltage breaker blown. Check breaker (located on bottom of interface
panel). If breaker blown, reset breaker.
-
Fault LED not operating. Loose connection at ignition module. Defective
LED. Check wiring connections. Check for continuity between FC1 And
FC2 on ignition control module using multimeter.
-
Ignition module locked out. Check LED diagnostic light MC display for
failure identification. See Fault Conditions for identification of fault codes.
Unit energized/Ignition module okay. Blower
NOT running.
-
Loose wire(s). Check wiring connection(s).
-
No call for humidity.
-
Defective or loose blower driver board. Check blower driver board for green
LED. Check if properly seated. Replace if properly seated but no LED.
-
Defective blower. Replace blower.
-
24VDC power supply defective or fuse blown. Check fuse on power supply.
Power to unit on, humidistat on, indicator lights
on except humidity demand.
-
Control signal miswired. Check signal.
-
Low water level. Check water supply.
-
Low float switch stuck or defective. Check continuity of float switch and
inspect floats. Clean floats if scaled up; replace if defective.
-
Bad control. Check LED for steady on or check MC display.
Pressure switch input okay but no trial for
ignition after purge delay.
-
Miswired. Check PSW terminal voltage.
-
Check for change of state when unit is turned down.
-
Bad control. Check LED for steady on.
Valve activates. No ignition. LED displays 3
flashes.
-
Defective hot surface ignitor. Check resistance (see service checks).
-
No gas supply, turn on gas.
-
Mis-wired ignitor. Check wiring.
-
Bad control. Replace.
Igniter on. No valve operation. LED displays 3
flashes
-
Valve wiring not connected. Connect.
-
Damaged valve coil. Replace valve.
-
Bad control. Check voltage between MV1 & ground. Replace control.
Valve activates. Ignition occurs, LED displays 3
flashes.
-
Defective flame sensor. Check flame current (see service checks).
-
S2 wire not connected or loose. Connect.
-
L1 and neutral wires to unit reversed. Correct polarity.
Flame with no call for heat.
-
Stuck valve. Shut off gas supply. Check LED for 2 flashes. Replace valve.
TROUBLESHOOTING GUIDE