increased static pressure (over 4.5" W.C.) will
result in hot water leaking down the drain.
Consult factory if this situation occurs.
5.
Where possible, mount humidifier at a height
convenient for servicing.
6.
Wall mounting brackets (provided with GH
100) should be securely attached open edge
upwards, horizontal, using field-supplied
fasteners (minimum of four 3/8" diameter
fasteners in each bracket). Attach to a
vertical, solid surface. Put a security bolt
through the hole provided in the back of the
cabinet so that the unit cannot be bumped off
the wall bracket. See Figure #3.
7.
Make sure humidifier is mounted level. If floor
mounted adjust using leveling legs.
All GH models are equipped with adjustable
leveling legs which have a maximum travel of
1.5”.
- These legs may be used to allow mounting of
an optional stand.
- These legs may be removed and replaced by
longer legs. Factory approval is needed.
- Removal or adjustment of legs requires a
1 1/8” wrench.
- 4 -
Figure #3
min.
915
mm/36”
(min.
50
mm/2”)
**
80
0m
m
(min.
50
mm/2”)**
**
800
mm/31.5”
DV
DV: Optional Direct Vent option
**: Space required for combustion air below or at the back of the unit.
Front
TOP
RIGHT
BOTTOM
Figure #2