Troubleshooting
6-13
P/N 7105144G
2008 Nordson Corporation
VersaBlue_NW
Level (Fixed Measuring Points
−
5-point Sensor)
Warning Tank Overfilled
If the measuring point
Tank overfilled
is reached or exceeded for longer than
5 seconds, a warning is triggered.
Automatic Reset
When the level falls below the measuring point.
Warning Tank Level Low
When the level falls below the measuring point
Tank level low
for longer
than 5 seconds, a warning is triggered.
Automatic Reset
When the measuring point is reached.
Fault Tank Empty
When the level falls below the measuring point
Tank empty
for longer than
5 seconds, a fault is triggered.
Automatic Reset
When the measuring point is reached.
Fault Level Sensor Defective
The level sensor transmits a faulty signal for longer than 5 seconds.
Fault Level Sensor Failure
Triggered when a wire breaks.
Automatic Reset
After replacement of the defective sensor.