Setpoint
Undertemp.
warning
Undertemperature warning
2
°
C
D
Setpoint
Overtemp.
warning
Overtemperature warning
[1]
2
°
C
Setpoint
Overtemperature warning
[2]
235
°
C
455
°F
2
°
C
D
Troubleshooting
6-7
P/N 7105144G
2008 Nordson Corporation
VersaBlue_NW
Undertemperature and Overtemperature
−
Warning
−
Alarm Triggered
Alarm Reset
Undertemperature Warning Triggered
The temperature has fallen below the setpoint by more than the differential
value (
D
)
Undertemperature warning delta
for longer than 5 seconds.
Automatic Reset
The temperature has increased to 2
°
C (3.6
°
F) below the setpoint.
Overtemperature Warning Triggered
[1] The temperature has exceeded the setpoint by more than the differential
value (
D
)
Overtemperature warning delta
for longer than 5 seconds.
or
[2] 235
°
C (455
°
F) was exceeded for longer than 5 seconds.
Automatic Reset
The temperature has fallen to 2
°
C (3.6
°
F) above the setpoint.
Содержание VersaBlue VB Series
Страница 40: ...Introduction 2 14 P N 7105144G 2008 Nordson Corporation VersaBlue_NW...
Страница 66: ...Installation 3 26 P N 7105144G 2008 Nordson Corporation VersaBlue_NW...
Страница 150: ...Operation 4 84 P N 7105144G 2008 Nordson Corporation VersaBlue_NW...
Страница 174: ...Maintenance 5 24 P N 7105144G 2008 Nordson Corporation VersaBlue_NW...
Страница 236: ...Parts 8 2 P N 7105144G 2008 Nordson Corporation VersaBlue_NW...
Страница 250: ...Options 10 6 P N 7105144G 2008 Nordson Corporation VersaBlue_NW...
Страница 254: ...Password A 4 P N 7105144G 2008 Nordson Corporation VersaBlue_NW...
Страница 280: ...Glossary D 16 P N 7105144G 2008 Nordson Corporation VersaBlue_NW...