Installation and Maintenance Manual Nimbra 300 Series
Installation
•
33
©2006 Net Insight AB, All rights reserved
Caution:
To avoid exceeding the environmental requirements above and
allow for enough air circulation around the switch, make sure
that a minimum distance of 10 cm (4 inch) is kept free, on left
and right side of the switch.
Installation
Unpacking and Inspection
Inspect the Nimbra 300 series switch upon reception. Notify the carrier and
dealer if there is damage. The packaging is recyclable; save for reuse or dispose
properly.
Installation Requirements
To ensure a correct installation, read this section to determine the environmental,
electrical, spatial and interface requirements.
Mechanical Requirements
•
Height: 88mm (3.5 inch)
•
Width: 445 mm (17.5 inch)
•
Depth: 240 mm (9.4 inch)
The switch is intended to be mounted in a 19-inch rack.
Environmental Requirements
•
Operating temperature
5 to 40 ºC (41 to 104 ºF)
•
(short term)
-5 to 55 ºC (23 to 131 ºF)
•
Storage temperature.
-40 to 70ºC (-40 to 156 ºF)
•
Relative humidity
10% to 90% (non-condensing)
•
Select a clean and dust free location for the unit
The Nimbra 300 series switch must be kept in a Restricted Access Location
(RAL).