62 NCB Service Manual
Version 1.0
4.9.3
Thermistor
Item
Description
Function
Measure hot and cold water temperature at the boiler’s space heating outlet and inlet
connections.
Fault
Inaccurate water temperatures from inside the boiler.
Symptoms
1.
If a thermistor fails, an error code is displayed before the boiler operates.
2.
If resistance values are outside the allowable range, there will be hot water temperature
fluctuations.
Error codes
E047, E205, E218, E407, E421
Diagnostics
1.
Visual inspection: Check wire connections are secure and inspect for wire damage.
2.
Test the resistance of the sensor. Before testing, shut down the boiler and allow it to cool.
Testing/inspection
information
Resistance range: Refer to the table below
Test for an open hot water temperature sensor (Test result: MΩ open)
Temp (
℃
)
Thermistor (kΩ)
[Space heating line]
Thermistor (kΩ)
[DHW line]
Exhaust Limit Temperature
Sensor (kΩ)
0-5 23.4-19.1
27.5-22.2
162.3-125.9
6-10 18.3-15.5
21.2-18.0
119.8-98.5
11-15 14.8-12.6
17.3-14.7
93.8-77.6
16-20 12.1-10.7
14.2-12.1
74.0-61.6
21-25 10.3-8.5
11.6-10.0
58.8-49.2
26-30 8.2-7.0
9.6-8.3
47.1-39.5
35-40 6.8-4.9
8.0-6.9
37.9-32.0
Содержание NCB-24LSWE
Страница 16: ...14 NCB Service Manual Version 1 0 NCB 24 28 34LSWE...
Страница 17: ...NCB Service Manual 15 Version 1 0 NCB 40LSWE...
Страница 18: ...16 NCB Service Manual Version 1 0 NCB 40LSWE...
Страница 60: ...58 NCB Service Manual Version 1 0 4 8 Electrical Diagnostic Contacts and Wiring Diagram...
Страница 87: ...NCB Service Manual 85 Version 1 0 Scenario2...
Страница 120: ...118 NCB Service Manual Version 1 0 5 2 24 782Error Error occurrence conditions and check items...
Страница 140: ...138 NCB Service Manual Version 1 0 Memo...
Страница 141: ...NCB Service Manual 139 Version 1 0 Memo...
Страница 142: ...140 NCB Service Manual Version 1 0 Memo...
Страница 143: ...NCB Service Manual 141 Version 1 0 Memo...
Страница 144: ...142 NCB Service Manual Version 1 0 Memo...