NCB Service Manual 61
Version 1.0
4.9.2
High Temperature Limit Switch
Item
Description
Function
1.
Overheat prevention switch.
2.
If the switch detects extremely high temperature, the boiler will automatically trip and shut
down.
3.
Excessive high water temperatures (> 105°C) in the heat exchanger will activate the high
limit switch.
Fault
Unable to detect high water temperature conditions if the switch malfunctions.
Symptoms
Unable to shut down the boiler if the water temperature from the heat exchanger exceeds 105°C.
Error codes
E016, E046
Diagnostics
1.
Visual inspection: Check wire connections are secure and inspect for wire damage.
2.
Resistance test: Confirm that the resistance is within the specification shown below.
Testing/inspection
information
Resistance range: < 1.0 Ω