NCB Service Manual 109
Version 1.0
5.2.15
Error 352
Error conditions and checklist
Error
Description
E352
High water
pressure
If an error signal is received from the water pressure sensor, the system displays the ‘E352’ on the front
panel. High water pressure errors occur if the water pressure is 3.9 bar or higher for 3 sec.
The error is automatically cancelled if the water pressure returns to 3.9 bar or lower.
Checklist
1.
Check if the input water pressure sensor is wet for any reason, including leakage.
2.
Check the controller
Testing method
Fault
Possible Causes
Check method
E352
High water pressure
Check the water supply pressure. (3.9 bar or higher is the error state)
Check if the safety valve is stuck.
Check the Auto feeder valve.
High water
pressure sensor
Water pressure
sensor fault
1.
Check the output voltage. (Normal state: 0.25-- 4.93 V)
2.
Replace the faulty or open water pressure sensor.
Содержание NCB-24LSWE
Страница 16: ...14 NCB Service Manual Version 1 0 NCB 24 28 34LSWE...
Страница 17: ...NCB Service Manual 15 Version 1 0 NCB 40LSWE...
Страница 18: ...16 NCB Service Manual Version 1 0 NCB 40LSWE...
Страница 60: ...58 NCB Service Manual Version 1 0 4 8 Electrical Diagnostic Contacts and Wiring Diagram...
Страница 87: ...NCB Service Manual 85 Version 1 0 Scenario2...
Страница 120: ...118 NCB Service Manual Version 1 0 5 2 24 782Error Error occurrence conditions and check items...
Страница 140: ...138 NCB Service Manual Version 1 0 Memo...
Страница 141: ...NCB Service Manual 139 Version 1 0 Memo...
Страница 142: ...140 NCB Service Manual Version 1 0 Memo...
Страница 143: ...NCB Service Manual 141 Version 1 0 Memo...
Страница 144: ...142 NCB Service Manual Version 1 0 Memo...