
NCB Service Manual 73
Version 1.0
4.9.14
Circulation Pump
Item
Description
Function
1.
Provides internal or external water circulation.
2.
Internal circulation minimises the effects of temperature fluctuations. External circulation
quickly delivers hot water to taps and results in water conservation.
Fault
Unable to detect or measure water flow.
Symptoms
1.
Water inside the boiler system freezes.
2.
Water temperature fluctuations when the boiler is set to internal recirculation.
3.
Hot water takes a long time to be available at taps when the boiler is set to external
recirculation.
Error codes
-
Diagnostics
1.
Visual inspection: Check the circulation pump connection wire.
2.
Check the water filter for obstructions.
3.
Voltage test: Test the voltage meets the specifications shown below.
Testing/inspection
information
YELLOW-WHITE
ON: AC 230 V
OFF: 0 V
Содержание NCB-24LSWE
Страница 16: ...14 NCB Service Manual Version 1 0 NCB 24 28 34LSWE...
Страница 17: ...NCB Service Manual 15 Version 1 0 NCB 40LSWE...
Страница 18: ...16 NCB Service Manual Version 1 0 NCB 40LSWE...
Страница 60: ...58 NCB Service Manual Version 1 0 4 8 Electrical Diagnostic Contacts and Wiring Diagram...
Страница 87: ...NCB Service Manual 85 Version 1 0 Scenario2...
Страница 120: ...118 NCB Service Manual Version 1 0 5 2 24 782Error Error occurrence conditions and check items...
Страница 140: ...138 NCB Service Manual Version 1 0 Memo...
Страница 141: ...NCB Service Manual 139 Version 1 0 Memo...
Страница 142: ...140 NCB Service Manual Version 1 0 Memo...
Страница 143: ...NCB Service Manual 141 Version 1 0 Memo...
Страница 144: ...142 NCB Service Manual Version 1 0 Memo...