45
START
2.2.4 Start Up
Purpose: Describes the Start Up procedure.
START UP FINISHED
Turn OFF:
All Loads, the AC Input & Output,
Battery and Utility Power circuit
breakers
Perform a self-test (see Section 2.2.3)
Turn ON the battery circuit breaker
Standby will be displayed on the LCD
Turn ON the AC input & output circuit
breaker. It will take 30 seconds for the
unit to go to Line mode from Standby
mode (see Section 2.2.2)
Turn On the upstream utility input circuit
breaker
One at a time, turn ON the output /
loads
Watch the Alarm LED. If it lights up or
flashes, stop turning on the loads and
follow this troubleshooting sequence:
1.
Investigate the Alarm.
2.
Perform a self-test with the load(s)
connected.
3.
If it passes the self-test, verify that the
load(s) are operating normally.
4.
See the trouble- shooting chart
Section
(
2.4.3)
5.
Contact
Myers Emergency Power
Systems
technical support.
Warning: Never run the MP2000E when
it is overloaded. Damage to its inverter,
batteries or unexpected shutdowns may
result.
If the unit detects a load greater than
VA, it automatically shuts itself
2000
down after 3 minutes.
Содержание MP Series
Страница 3: ...III ...
Страница 20: ...20 STEP 1 Connect CONTROL Wires ...
Страница 22: ...22 Installation and Troubleshooting Guide Figure 9 ...
Страница 30: ...30 MP2000E System Battery Backup System Section 2 Operator s Manual ...
Страница 49: ...49 Figure 21 Note See Section 2 2 14 For details on Event Log View under Maintenance submenu ...
Страница 51: ...51 2 2 8 Status Submenu CONT D ...
Страница 70: ...70 2 3 3 Main Menu ...
Страница 72: ...2 3 4 1 RS232 USB Menu Tree ...
Страница 74: ...74 ...
Страница 104: ...104 Figure 6 70 SMS for Event Log Screen ...
Страница 126: ...126 ...
Страница 148: ...148 ...